Daikin RZQ100B7W1B [7/48] Outdoor units r410a rzq b

Daikin RZQ125B8V3B [7/48] Outdoor units r410a rzq b
2
2
Split Sky Air • Outdoor Units
5
Outdoor Units • R410A • RZQ-B
Motor Speed (nominal at
230V)
Steps 8 8 8 8
Cooling rpm 782 782 760 760
Heating rpm 767 767 825 825
Fan Motor Output W 70 70 750 750
Drive Direct drive
Compressor Quantity 1 1 2 2
Motor Model JT1G-VDYR@T JT1G-VDYR@T Inverter
Type Hermetically sealed scroll compressor
Speed rpm - - 900~6480
Motor
Output
W 2200 2200 2200 2200
Starting Method Direct on line
Crankcase
Heater
W33333333
Motor Model - - ON - OFF
Type Hermetically sealed scroll compressor
Speed rpm - - 2900
Motor
Output
W- - 4500
Starting Method Direct on line
Crankcase
Heater
W- - 33
Operation Range Cooling Min °CDB -15.0 -15.0 -5.0 -5.0
Max °CDB 50.0 50.0 46.0 46.0
Heating Min °CWB -20.0 -20.0 -15.0 -15.0
Max °CWB 15.5 15.5 15.0 15.0
Sound Level
(nominal)
Cooling Sound
Power
dBA 66.0 66.0 - -
Sound
Pressure
dBA 50.0 50.0 - -
Heating Sound
Power
dBA - - 78.0 78.0
Sound
Pressure
dBA - - 57.0 57.0
Sound Level
(Night quiet)
Cooling Sound
Pressure
dBA 45.0 45.0 - -
Refrigerant Type R-410A
Charge kg 4.30 4.30 8.00 9.00
Control Expansion valve (electronic type)
Nr of Circuits 1 1 1 1
Refrigerant Oil Type Daphne FVC68D
Charged Volume l 1.0 1.0 1.7 + 1.6 1.7 + 1.6
Piping
connections
Liquid (OD) Quantity 1 1 1 1
Type Flare connection
Diameter
(OD)
mm 9.52 9.52 9.52 12.7
Gas Quantity 1 1 1 1
Type Flare connection Braze connection
Diameter
(OD)
mm 15.9 15.9 22.2 22.2
Drain Quantity 3 3 - -
Type Hole - -
Diameter
(OD)
mm 26 26 - -
Piping Length Minimum m 5 5 5 5
Maximum m 75 75 100 100
Equivalent m 95 95 - -
Chargelessm30303030
Additional Refrigerant Charge kg/m see installation manual 4PW21412-1
Installation height
difference
Maximum m 30.0 30.0 30.0 30.0
Max. internunit level difference m 0.5 0.5 0.5 0.5
Heat Insulation Both liquid and gas pipes
Defrost Method Pressure equalising Reversed cycle
Defrost Control Sensor for outdoor heat exchanger temperature Sensor for outdoor heat exchanger temperature
Capacity Control Method Inverter controlled Inverter controlled
2-1 TECHNICAL SPECIFICATIONS
RZQ125B7W1B RZQ140B7W1B RZQ200B7W1B RZQ250B7W1B