Daikin RZQ45KCVJK [10/64] 3 in case of stacked installation units mm

Daikin RZQ45KCVJK [10/64] 3 in case of stacked installation units mm
9 English
2. When something is obstructing the top.
Relation of dimensions of H, A, and L are shown in the table below.
Get the lower part of the frame sealed so that air from the outlet does
not bypass.
Only two units at most can be installed in series.
Pattern 2 Where obstacles in front of the air outlet is lower than the unit.
1. When nothing is obstructing the top.
(There is no height limit for obstructions on the intake side.)
Relation of dimensions of H, A, and L are shown in the table below.
2. When something is obstructing the top.
Relation of dimensions of H, A, and L are shown in the table below.
Get the lower part of the frame sealed so that air from the outlet doe
s
not bypass.
Only two units at most can be installed in series.
If the dimensions excee
d the values in the brackets, the stand does not have to be installed even when H
is lower than L.
4-3 IN CASE OF STACKED INSTALLATION (Units : mm)
1. In case obstacles exist in front of the outlet side.
AL
L H
0 < L 1/2H 1000 or more
1/2H < L H 1250 or more
L > H
Set the frame to be L H
Refer to the column of L H for A
AL
0 < L 1/2H 150 (250) or more
1/2H < L H 200 (300) or more
AL
L H
0 < L 1/2H 150 (250) or more
1/2H < L H 200 (300) or more
L > H
Set the frame to be L H
Refer to the column of L H for A
200 or more
(300)
1000 or more
500 or less
A
L
H
100 or
more
1000 or more
(1500)
A
H
L
100 or
more
100 or
more
1000 or more
(1500)
1000 or more
500
or less
A
H
L
100 or
more
01_EN_3P281953-1B.fm Page 9 Tuesday, January 25, 2011 3:35 PM
In case obstacles exist in front of both the air inlet and outlet sides
Pattern 1 Where obstacle in front of the air outlet is higher than the unit.
1. When nothing is obstructing the top.
(There is no height limit for obstructions on the intake side.)
200 or more
(300)
H
L
L>H
1000 or more
100 or
more
100 or
more
1000 or more
500 or more
100 or
more
A