13 English
Precautions when re-using pre-existing refrigerant piping
Abide by the following when re-using pre-existing refrigerant piping. Any problems with the piping may lead
to malfunctioning.
In the following cases, do not re-use piping, but rather lay new piping.
· If indoor or outdoor units have been disconnected from the piping for a long time (as water and foreign
matter might have entered the piping).
· If copper piping is corroded.
Flares should be redone and not re-used, in order to prevent refrigerant leaks.
Do not reuse the flare nuts. Instead, use the flare nuts included with the pr
oduct.
Check for refrigerant leaks on welded areas if the pre-existing piping has been welded anywhere.
Replace any deteriorated insulation with new insulation.
6-2 INSTALLATION TOOLS
Be sure to use the dedicated tools to ensure sufficient pressure resistance and prevent the entry of
any impurities.
6-3 SELECTING PIPING MATERIALS
Use the piping whose inside and outside are clean and with no harmful substances for use such as sulphur,
oxide, dust, dust from cutting, grease, or liquid (contamination) is attached.
For the refrigerant piping, use the following material.
Material: Deoxidised phosphorous seamless copper pipe
Thickness and size: Decide based on section 6-5 REFRIGERANT PIPE SIZE AND ALLOWABLE PIPE
LENGTH.
For the handling of the stop valves, refer to “Precautions when the handling piping stop valves” in section
6-6 REFRIGERANT PIPING WORK.
Be sure to perform piping
work using measurements within the maximum allowable
length and height
difference
described in 6-5 REFRIGERANT PIPE SIZE AND ALLOWABLE PIPE LENGTH.
6-4 PIPING PROTECTION
Protect the piping and prevent liquid, dirt and dust from entering into the piping.
Pay special attention when running the copper pipe through the through-hole or when leading the edge of the
pipe outside the room.
Manifold gauge
Charging hose
To ensure sufficient pressure resistance and prevent the entry of any impurities (mineral
oils such as Suniso oil and liquids), use the R410A dedicated item (the screw specifica-
tions for R410A and R407C differ).
Vacuum pump
Be extremely careful not to flow the pump oil backward to in
side the piping when the
pump is stopped.
Use a pump whose gauge pressure can vacuum up to –0.1 MPa (–755 mmHg).
dohtem noitcetorPdoirep kroWnoitacoL
Outdoor
gnihcniPerom ro htnom enO
Less than one month Pinching or taping
dohtem noitcetorPdoirep kroWnoitacoL
gnipat ro gnihcniPA/NroodnI