Conversion Instructions
2 CONVERSION OF THE GAS RING
1. Switch off the electrical supply to the appliance
2. Close the gas tap on the gas supply to the appliance
3. Remove the front panel of the appliance
4. Disconnect the coupling above the gas valve and turn the gas mixing pipe backwards
5. Replace the original O-ring and the gas setting ring with the rings in the conversion set
6. Reconnect the coupling above the gas valve and open the gas tap
7. Check the gas connections for tightness/leaks
8. Switch on the electrical supply to the appliance
CAUTION
It is not possible to adjust the CO
2
level at high setting.
When the CO
2
level at high setting is not within the prescribed
tolerance band please contact your local Daikin or Rotex dealer.
For adjusting CO
2
level at low setting see § 3 .
9. Apply a sticker “gas type” (2 pcs. included in the conversion set) to the nut at the upper side of
the gas valve
10. Apply the second sticker “gas type” to the appliance plate (lower left corner) in such a way that
the original data referring to the gas type is covered.
11. Continue with checking the CO
2
setting of the boiler. See § 3 .
CAUTION
Checking the CO
2
setting of the boiler must be executed with the
front panel removed.
The maximum deviation of the flue gas analyser that is allowed is
± 0,3%.
During the check the installation location must not be under the
influence of over- or under pressure situations.
It is not possible to adjust the CO
2
value at maximum power..
When the value measured at maximum power falls without the
prescribed range the boiler has to be checked on gas tightness and
usage of the correct components, in particular the gas ring, the
insert and the fan.
When replacing parts that can affect combustion or conversion to
another gas type the CO
2
setting needs to be checked.
.