EKHY075787 / EKPS075867 / EKPS075877 / EKPS075917
EKPS076197 / EKPS 076207 / EKPS076217 / EKPS076227
Conversion Instructions
1. Remove the cover cap (A) on the gas valve so setting screw B will become
accessible.
2. Activate the test program for minimum output by simultaneously pressing
the buttons and . A capital L appears in the service display.
3. Wait until the reading of the analyser is stabilized (min. 3 minutes).
4. Measure the O2(L) or CO2(L) value.
5. Set the correct value for O2(L) or CO2(L) by turning setting screw B.
See table 4 or 5 for the correct value.
Choose the correct table. Table 4 is for Propane, table 5 is for
Natural Gas G25.
(CO2(H) is the value that has been noted during the measurement
on maximum output.
Turning the adjustment screw clockwise will raise the CO
2
value.
Turning anti clockwise will lower the CO
2
value.
Change the setting in small steps and wait until the reading is
stabilized before continuing.
Table 4: Determining the correct setting of CO
2
at minimum output for propane
G31 (front panel removed)
Propane 3P G31 (30 & 50 mBar)
Measured value am maximim power
(See § 3.1)
Prescribed value at minimum power
(= CO
2
(H) 0.3)
CO
2
(H) [%]
CO
2
(L) [%]
10.8
10.5 ±0.1
10.6
10.3 ±0.1
10.4
10.1 ±0.1
10.2
9.9 ±0.1
10.0
9.7 ±0.1
9.8
9.5 ±0.1
Table 5: Determining the correct setting of CO
2
at minimum output for natural
gas G25 (front panel removed)
Natural gas G25 (25 mBar)
Measured value am maximim power
(See § 3.1 )
Prescribed value at minimum power
(= 0.5 x CO
2
(H) + 4.2)
CO
2
(H) [%]
CO
2
(L) [%]
9.6
9.0 ±0.1
9.4
8.9 ±0.1
9.2
8.8 ±0.1
9.0
8.7 ±0.1
8.8
8.6 ±0.1
8.6
8.5 ±0.1
6. Reposition the cover cap A of the setting screw B for protection.
7. Repeat the measurement at maximum output (§ 3.1) to ensure the correct
operation of the boiler.
8. Place the front panel back on the boiler.
9. Activate the test program for maximum output by simultaneously pressing the
buttons and twice. A capital H appears in service display.
10. Check the CO value of the combustion to make sure no recirculation is taking
place.
11. Switch the appliance off with the button. [-] is shown in the service display.
12. Remove the measuring probe and reposition the cap X on the sampling point off
the adapter.
13. Switch the appliance on with the button .
14. Check if the central heating and (when available) DHW are working properly.