Daikin UATYA160BFC3Y1 [27/356] Relative humidity control with proportional control

Daikin UATYA160BFC3Y1 [27/356] Relative humidity control with proportional control
Translation from original instructions
Packaged Rooftop
27
We reserve the right to make changes without any prior notice.
UATYA
4P645203-1
The value set in parameter “HU11” identies the reference humidity value, as follows:
- 0 = relative humidity;
- 1 = absolute humidity.
5.4.1 Relative humidity control with proportional control
If parameter “HU11” is set to “0”, humidity control is performed according to the relative humidity value.
Relative humidity is managed according to parameter “HU14”, which identies the probe on which the controller
must guarantee maintenance of the entered setpoint, and on parameter “HU12” that determines the type of humidity
control.
The parameters involved are shown in the table.
The values of the parameters are representative. In specic cases, di󰀨erent values can be set.
Parameter Value UM Description
HU4 5.0 % Relative humidity control di󰀨erential
HU5 0.5 % Relative humidity control neutral area
A graphical representation is shown below.
HU4
100
0
%
HU4
HU5
HU1
SdR %
HU5
Fig. 9 Relative humidity control