5.8 Damper management
In addition to air change in the room, the controller can also manage other functions connected to comfort enhancement
and system economy.
The functions the controller can handle vary according to the number of dampers tted in the unit:
- units with 2 dampers, for fresh air only;
- units with 3 dampers, when free cooling / free heating is featured;
- units with 4 dampers, when a heat recovery system is tted in addition to free cooling / free heating.
Dampers can be set either linearly or proportionally.
Units with two dampers
The dampers featured in 2-damper units include: a damper for fresh external air and a damper for recirculated air.
Normally, their operation is complementary, i.e. the percentage opening of the external air damper is equal to the
percentage closing of the recycled air damper.
Units with three dampers
The dampers featured in 3-damper units include: a damper for fresh air, a damper for exhaust air and a damper for
recirculated air.
Normally, the external air damper opens at the same percentage as the exhaust air damper and the recycled air
damper is complementary to the other two. So, the percentage opening of the external air damper and the exhaust
air damper is equal to the percentage closing of the recycled air damper.
Units with four dampers
Units with four dampers feature the same dampers as 3-damper units plus one. The fourth damper is used for
external air.
It is used to cause the external air to ow through the heat recovery system, when heat recovery is enabled, and it is
closed in free cooling mode.
If the heat recovery system is not sized to provide for a 100% air ow in the unit, a fth damper is actually tted. This
is an extra exhaust damper that is used by the unit in free cooling mode to bypass the heat recovery system.
The parameters involved are shown in the table.
Parameter Min Max UM Description
DA43 0.0 50.0 °C
External air - Opening reduction for external air temperature -
Summer temperature threshold
DA44 -20.0 16.0 °C
External air - Opening reduction for external air temperature - Winter
temperature threshold
DA45 0 100 %
External air - Opening reduction for external air temperature - Min
opening
DA52 0 3 - External air - Start up - Conguration
DA54 0 999 min External air - Start up - Wash duration