131
Daikin Altherma Low Temperature • Outdoor units • ERLQ011-016BAW1
8 Installation
8 - 1 Installation method
8
8
3TW59559-1
Do not stack more than one unit.
About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe.
Get the portion A sealed so that air from the outlet does not bypass.
2. Installing multiple units (2 units or more) in lateral connection per row
1. Obstacles exist in front of the outlet side
1. Installation of one unit per row
ERLQ011-016BW1
A. Non stacked installation
2. Obstacles exist in front of the air inlet
B. Stacked installation
Legend unit (mm)
C. Multiple-row installation
Relation of dimensions of H, A, and L are shown in the
table below.
LA
L H
0<L 1/2 H 250
1/2 H < L 300
H < L Installation not allowed
Suction side obstacle
Discharge side obstacle
Left side obstacle
Right side obstacle
Top side obstacle
Obstacle is present
In these cases, close the bottom of
the installation frame to prevent
discharged air from being
bypassed.
In these cases, only 2 units can be
installed.
This situation is not allowed.
1
2