Daikin LRMEQ5AY1E [14/127] 4 procedure for wiring inside units

Daikin LRMEQ8AY1 [14/127] 4 procedure for wiring inside units
12 English
Z
sys
less than or equal to Z
max
and
S
sc
greater than or equal to the minimum S
sc
value.
(1) European/International Technical Standard setting the limits for
voltage changes.
voltage llucruations and flicker in public low-voltage supply sys-
tems for equipment with rated current 75A
(2) European/International Technical Standard setting the limits for
harmonic currents produced by equipment connected to public
low-voltage systems with input current > 16A and 75A per
phase.
Warning, alarm, and operation output wiring connections
Connect warning, alarm, and operation output wiring to the X2M
terminal block and clamp as indicated by the following diagram:
X2M wire specifications
CAUTION
Refer to the “7-1 Example of Wiring Entire System” by all means
when connecting the operation output wiring.
A compressor failure may result if the operating output wiring is
not connected.
Remote operating switch wiring connections
When installing a remote operating switch, clamp as indicated by
the following diagram:
X3M wire specifications
CAUTION
For Remote switch, use non-voltage contact for microcurrent (not
more than 1mA, 12VDC)
If the remote operating switch will be used to start and stop the
unit, set the operating switch to “REMOTE”.
Precautions for Terminal Connections
Be sure to use ring-type crimp-style terminals provided with insu-
lation sleeves.
Use specified electric wires for the wiring and secure the wiring so
that external force will not be imposed on the terminal block.
Use an appropriate screwdriver to tighten the terminal screws.
Small-sized screwdriver will damage the screw heads and cannot
tighten the screws properly.
Do not tighten the terminal screws in excess, otherwise the
screws may be damaged.
Refer to the following table for the tightening torque values of the
terminal screws.
Take out the earth wire from the notch of the cup washer and lay
the wire carefully so that other wires will not be caught by the
washer. Otherwise, the earth wire may not contact sufficiently and
the earthing effect of the wire may be lost.
Do not finish strand wire with solder.
7-4 Procedure for Wiring Inside Units
Referring to the following figure, secure and wire the power and
transmission wiring using the accessory clamp (1), (2), and (3).
Lay the ground wire so that it will not come in contact with the lead
wires of the compressor. Other equipment will be adversely
affected if the ground wire comes in contact with the lead wires of
the compressor.
Make sure all wiring do not contact to the pipes (hatching parts in
the figure).
The transmission wiring must be at least 50 mm away from the
power wiring.
After wiring work is completed, check to make sure there are no
loose connections among the electrical parts in the control box.
Z
max
() minimum S
sc
value
LRMEQ5AY1
LRLEQ5AY1
––
LRMEQ6AY1
LRLEQ6AY1
––
LRMEQ8AY1
LRLEQ8AY1
0.27 652KVA
LRMEQ10AY1
LRLEQ10AY1
0.27 896KVA
LRMEQ12AY1
LRLEQ12AY1
0.27 1093KVA
LRMEQ15AY1
LRLEQ15AY1
0.24 757KVA
LRMEQ20AY1
LRLEQ20AY1
0.24 941KVA
Electric wire thickness
0.75~1.25mm
2
Max. wiring length 130m
C1 W1
C
P2
P1
Mount insulation sleeves
Fix the wiring with the
provided clamp (1)
X2M
X3M
2
1
Secure remote
operating switch
wiring to the resin
block using a clamp
(field supply).
Electric wire thickness
0.75~1.25mm
2
Max. wiring length 130m
Screw size Tightening torque (N•m)
M8 (Power supply terminal block)
5.5 - 7.3
M8 (Earth)
M4 (X2M) 2.39 - 2.91
M3.5 (X3M) 0.79 - 0.97
Crimp-style terminal
Insulating sleeve
Power wire
Crimp-style terminal
Cup washer
Cut out section
01_EN_3P248411-2.fm Page 12 Monday, June 8, 2009 12:28 PM