Daikin LRMEQ8AY1 [103/156] Troubleshooting

Daikin LRMEQ8AY1E [103/156] Troubleshooting
Troubleshooting SiENBE28-901
102 Air Cooled Refrigeration Condensing Unit
Troubleshooting
*1.List of relevant malfunction codes and connectors
Malfunction
code
Relevant thermistor
LRMEQ5, 6AY1
LRLEQ5, 6AY1
LRMEQ8, 10, 12AY1
LRLEQ8, 10, 12AY1
LRMEQ15, 20AY1
LRLEQ15, 20AY1
Electrical
symbol
Connector
Electrical
symbol
Connector
Electrical
symbol
Connector
H9
Outdoor air thermistor R1T X18A R1T X18A R1T X18A
J3
Discharge pipe (M1C)
thermistor
R31T X29A R31T
X29A
R31T
X29A
Discharge pipe (M2C)
thermistor
R32T R32T
Discharge pipe (M3C)
thermistor
————R33T
J5
Suction pipe thermistor R2T
X30A
R2T
X30A
R2T
X30A
J8
Heat exchanger outlet
thermistor
R5T R5T R5T
J9
Heat exchanger inlet
thermistor
R6T R6T R6T
JA
High pressure sensor S1NPH X32A S1NPH X32A S1NPH X32A
JC
Low pressure sensor S1NPL X31A S1NPL X31A S1NPL X31A
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
*Three or more sensors malfunction.
Check for the malfunction
history (malfunction code) on
the remote controller to identify
three or more malfunctioning
sensors. (See*1)
Check the malfunctioning
sensor identified for their
connector connection.
Is the resistance
normal? (*1)
YES
NO
Troubleshoot according to the
malfunction code of each
malfunction sensor. (See the
flowchart corresponding to
each malfunction code.)
Is the resistance
normal?
NO
Properly connect it.
Replace the relevant sensor.
Replace the outdoor unit PCB
(control PCB).