Field Settings SiENBE28-901
36 Air Cooled Refrigeration Condensing Unit
b-1. Setting mode 2
The number in the “No.” column represent the number of times to press the SET (BS2) button.
No.
Display of setting items
Display of setting conditions
Setting item H1P H2P H3P H4P H5P H6P H7P
0
ΔTsp: Fine-tuning setting of
evaporation temperature
khhhhhh
2 Current limitation setting
khhhhkh
3
Setting of limit value of outdoor fan
taps
khhhhkk
5
Setting of external low noise
operation
(Tax1, 2 and Tay1, 2 are set by
setting 2-21. )
khhhkhk
6 AIRNET address
khhhkkh
7
Setting of night-time low noise
operation (Only connected to
AIRNET)
khhhkkk
8
Night-time low noise start setting.
It uses it for setting 2-7 and 2-11.
(Only connected to AIRNET)
khhkhhh
9
Night-time low noise end setting.
It uses it for setting 2-7 and 2-11.
(Only connected to AIRNET)
khhkhhk
11
ΔTsn: Evaporation temperature
correction setting during
operation at night-time
khhkhkk
21
Setting of external temperature of
outdoor fan tap
It uses it by setting 2-5.
khhkkhk
40
Setting of high static pressure of
outdoor fan
khkhhhk
(*1) Standard setting High static pressure setting
Model name LRM(L)EQ6,12,20AY1 LRM(L)EQ5,8,10,15,20AY1 LRM(L)EQ6,12,15,20AY1 LRM(L)EQ5,8,10AY1
Factory set 9 9 8 8
Setting 1 8 10 7 9
Setting 2 7 8 6 7
Setting 3 6 7 5 6
Setting 4 5 6 5 5
Setting 5 5 5 5 5
H1P H2P H3P H4P H5P H6P H7P
ΔTsp
0K (Factory set) khhhhhh
-1°C khhhhhk
-2°C khhhhkh
-3°C khhhhkk
-4°C khhhkhh
-5°C khhhkhk
+1°C khhhkkh
+2°C khhhkkk
+3°C khhkhhh
+4°C khhkhhk
+5°C khhkhkh
LRM(L)EQ
H1P H2P H3P H4P H5P H6P H7P
5,6AY1
8,10,12AY1
15,20AY1
No limitation. (Factory set)
khhhhhk
10A 20A 36A khhhhkh
9A 18A 30A khhhkhh
7A 14A 27A khhkhhh
H1P H2P H3P H4P H5P H6P H7P
Details
depend on
the
following.(*1)
(Factory set)
khhhhhk
Setting 1 khhhhkh
Setting 2 khhhkhh
Setting 3 khhkhhh
Setting 4 khkhhhh
Setting 5 kkhhhhh
H1P H2P H3P H4P H5P H6P H7P
6 (TambTax1)
7(Tay1<TambTax2)
9(Tamb<Tay2) (Factory set)
khhhhhk
5(TambTax1)
6(Tay1<TambTax2)
9(Tamb<Tay2)
khhhhkh
H1P H2P H3P H4P H5P H6P H7P
Please give the
address of 1 or
more when you do
the AIRNET.
Binary system for
address(six digits)
(Factory set) 0
khhhhhh
1 khhhhkk
~
63 khkkkkk
Standard
setting
High static
pressure setting
H1P H2P H3P H4P H5P H6P H7P
99khhhhhk
87khhhhkh
78khhhkhh
66khhkhhh
55khkhhhh
44kkhhhhh
H1P H2P H3P H4P H5P H6P H7P
21:00 (Factory set) khhhhhk
22:00 khhhhkh
23:00 khhhkhh
20:00 khhkhhh
H1P H2P H3P H4P H5P H6P H7P
7:00 (Factory set) khhhhhk
8:00 khhhhkh
9:00 khhhkhh
6:00 khhkhhh
As for Factory set, time zone between 2-8 and 2-9 becomes effective for setting.
H1P H2P H3P H4P H5P H6P H7P
+1°C(Factory set) khhhhhk
+2°C khhhhkh
+3°C khhhkhh
0°C khhkhhh
Tax1 Tay1 Tax2 Tay2 H1P H2P H3P H4P H5P H6P H7P
26°C 28°C 31°C 33°C khhhhhk
20°C 22°C 26°C 28°C khhhhkh
27°C 29°C 32°C 34°C khhhkhh
H1P H2P H3P H4P H5P H6P H7P
Standard setting
(Factory set)
khhhhhk
High static
pressure setting
khhhhkh