Troubleshooting SiENBE28-901
82 Air Cooled Refrigeration Condensing Unit
[Data]
[Amp/Fin]
[Irregular stop]
Mark on RAM Monitor Meaning (Calculation value from sensor)
SH Suction super heat
TdSH1 Discharge super heat(INV)
TdSH2 Discharge super heat(STD1)
TdSH3 Discharge super heat(STD1)
Lpm
Target evaporation temperature equivalent pressure
(Lpm is saturation temperature equivalent pressure of Tst.
Tst=f(Lpm)=Tsd+ΔTsp+ΔTsn=f(Lpm1)+f(ΔTm)+ΔTsn
Lpm1
Target evaporation temperature equivalent pressure
(Lpm1 is saturation temperature equivalent pressure of Tsd.)
ΔTm_ho ΔTm is an equivalent saturation pressure value of ΔTsp.
Mark on RAM Monitor Meaning
Inv_1_Amp The first inverter current
Inv_2_Amp The second inverter current
Fin_Temp Temperature of INV fin
Fan1_1_Amp The first fan1 current
Fan1_2_Amp The second fan1 current
Fan2_1_Amp The first fan2 current
Fan2_2_Amp The second fan2 current
Mark on RAM Monitor Meaning
Irregular stop Irregular stop bits (Normality/abnormality:0/1)
Inv_Abnomal_fixation
Inverter compressor abnormality and fixation bits(Normality/abnormality:0/1)
STD1_Abnomal_fixation
STD1 compressor abnormality and fixation bits(Normality/abnormality:0/1)
STD2_Abnomal_fixation
STD2 compressor abnormality and fixation bits(Normality/abnormality:0/1)
FAN1_Abnomal_fixation
FAN1 compressor abnormality and fixation bits(Normality/abnormality:0/1)
FAN2_Abnomal_fixation
FAN2 compressor abnormality and fixation bits(Normality/abnormality:0/1)