Daikin LRMEQ8AY1 [31/156] Field settings

Daikin LRLEQ15AY1E [31/156] Field settings
Field Settings SiENBE28-901
30 Air Cooled Refrigeration Condensing Unit
3. Field Settings
3.1 Field Setting From Outdoor Unit
The target evaporation temperature can be calculated as follows:
Tst : Target evaporation temperature
Tsd : Evaporation temperature set by dip switches
ΔTsp: Temperature correction setting by pushbuttons.
ΔTsn: Temperature correction setting during night-time operation
The evaporation temperature can be set by dip switches and pushbuttons on the outdoor unit
PCB.
The dip switches can be set when the power is turned off, while the pushbuttons can be set
while the condensing unit is operating.
Note that the actual evaporation temperature may be lower than that specified, if the outdoor
temperature is too low. (This is intended to protect the compressors.)
Do not set the evaporation temperature to less than the values below. (This may damage the
compressors.)
MT series : -20°C
LT series : -45°C
(1) Field settings by dip switches
Be sure to turn off the power before changing the DIP switch settings.
DS1-1 to 3 enable setting the saturated temperature equivalent to suction pressure (in
increments of 5°C).
Do not change the settings of DS1-4, DS2-1 to 4.
Tst = Tsd + ΔTsp + ΔTsn
Location of soft switches
Location of dip switches
DS1 DS2
ON
OFF
Dip switches 1 to 3
1234 5678
The evaporation temperature setting
(specified using the dip switches) can
be changed using the pushbuttons,
within the range of -4K to +4K, in steps
of about 1K. Refer the setting method
on next page.
Switch box
Main PCB