Daikin LRMEQ8AY1 [9/156] Air cooled refrigeration condensing unit

Daikin LRMEQ10AY1 [9/156] Air cooled refrigeration condensing unit
Standard Specification SiENBE28-901
8 Air Cooled Refrigeration Condensing Unit
Notes:
H1 [ ] shows the anti-corrosion treatment type.
H2 Rated conditions of the refrigeration equipment :
Saturated temperature equivalent to suction pressure: -10°C
Outdoor air: 32°C, Suction SH: 10°C
H3 Measurement place: Front: 1m, Height: 1.5m
4 The minimum connection load with inside unit: 2.0kW
Model 1
LRMEQ8AY1
[LRMEQ8AY1E]
LRMEQ10AY1
[LRMEQ10AY1E]
LRMEQ12AY1
[LRMEQ12AY1E]
Power Supply 3 phase 50Hz 380-415V
Capacity 2 kW 18.6 21.8 24.4
Range of Suction Pressure Equivalent
Saturation Temperature
°C -20~+10
Range of Outdoor Temperature °C -15~+43
Casing Color Ivory white (5Y7.5/1) [Light camel (2.5Y6.5/1.5)]
Dimensions: (H×W×D) mm 1680×930×765
Heat Exchanger Cross fin coil
Compressor
Type Hermetically sealed scroll type
Piston Displacement m
3
/h 19.68 23.36 25.27
Number of Revolutions r.p.m 4320, 2900 6060, 2900 6960, 2900
Motor Output × Number of Units
kW 2.1+3.6 3.0+3.6 3.4+3.6
Starting Method Direct-on-line (Inverter system)
Fan
Type Propeller fan
Motor Output kW 0.75×1
Air Flow Rate
m
3
/min
171 179 191
Drive Direct drive
Connecting
Pipes
Liquid Pipe φ9.5 C1220T (Brazing connection)
Gas Pipe φ25.4 C1220T (Brazing connection)
Receiver Volume 8.1
Mass kg 255
Safety Devices
High Pressure Switch, Fan Driver Overload Protector, Overcurrent Relay,
Inverter Overload Protector, Fusible Plug
Capacity Control % 17~100 14~100 13~100
Refrigerant
Refrigerant Name R410A
Charge Volume kg 7.9
Refrigerant
Oil
Refrigerant Oil Name DAPHNE FVC68D
Charge Volume L 1.7+2.1+3.0
Operating Sound 3 dBA 57 59 61
Standard Accessories Installation Manual, Operation Manual, Connection Pipes, Clamps