Haier AE182FCAKA [134/174] Charge through air outlet or inspecting hole 1200ccd water to see water drainage

Haier AE182FCAHA [134/174] Charge through air outlet or inspecting hole 1200ccd water to see water drainage
5.3.6 Installation of drainage pipe
1-1.5m
Use the self-provided stiff pipe and clip with unit. Insert water pipe into water plug until it reaches the white tape.
Tighten the clip until head of the screw is less than 4mm from hose.
Wind the drain hose to the clip using seal pad 8 .
Insulate drain hose in the room.
2
<Cautions for the drain water lifting pipe>
Clip
2
Tape (White)
Self-provided stiff pipe
Clip
2
4mm below
(accessory)
(accessory)
Large size seal pad
Clip
2
10
Installation height shall be less than 280mm.
There should be a right angle with unit, 300mm from unit.
Waterring can of plastic
(1) Install water drainage pipe
Pipe dia, shall be equal or larger than that of unit piping.(pipe of polyethylent; size: 25mm; O.D:32mm)
Drain pipe should be short, with a downward slope at least 1/100 to prevent air bag from happening.
If downward slope can't be made, take other measures to lift it up.
Keep a distance of 1-1.5m between suspending brackets, to make water hose straight.
Slope over 1/100
75 below
Self-provided stiff pipe
(accessory)
500 below
300mm below
1~1.5m
280 below
500 below
220
Drain hose 1
(accessory)
drain water lifting pipe
Suspending bracket
Clip
(accessory)
2
Over 100
(Note)
If several water hoses join together, do as per following proceedures.
Connect water hoses with a T joint.
Specifieations of the water hoses shall meet the requirements for the unit running.
The slope of water drain hose (1) shall be within 75mm, don't apply too much force on it.
Method of water charging
11
When wiring is not complete
Charge water from
air outlet
Charge water from
inspecting hole
Watering can of plastic
pipe should be about
100 mm long
100mm
Water drainage port for
maintenance
(Drain water from
this hole)
Self-provided stiff pipe
Maintenance
Inspecting hole
(2) Check if water drainage is smooth after installation.
Charge, through air outlet or inspecting hole, 1200ccd water to see water drainage.
After wiring
Remove cover of control box, short connect "CHECK" terminal of the indoor unit, which is on the uper
part of indoor unit PCB. Connect 1PH power to terminal 1 and 2 on terminal block.
Note, in this operation, fan will be running.
Upon confirmation of a smooth water drainage, be sure to cut off power supply andremove short
connection of "CHECK" terminal.
Check water drainage in cooling operation. See also test run.
INSTALLATION INSTRUCTIONS