Castel MAC HC 40 NTV Инструкция по эксплуатации онлайн [7/18] 272069

Castel MAC HC 40 NTV Инструкция по эксплуатации онлайн [7/18] 272069
7
GB
2.5 Notes for the installation engineer
Check the proper installation and system
testing before commissioning the
machine (test report).
1.Check any gas leaks from the welding or
joints made during the installation phase.
2.Check the good insulation of the connec-
tion pipes linking the condenser and the
remote condensing units.
3.Check the electrical connection.
4.Check the electrical input values.
5.Check the standard pressure of the
refrigeration plant.
6.Verify the plumbing connection with the
regulation of the pressure switch valve
during operation and the good circulation
of the condensate water (water-cooled
assemblies).
7.Check that the conservator reaches the
set temperature and perform a manual
defrosting.
If the equipment or the remote condens-
ing unit are not moved into position verti-
cally (e.g. on their backs) or they have
been overturned during installation, do
not turn on immediately but wait at least
four hours before operating.
Inform the customer how the equipment
should be used exactly with specific ref-
erence to the use and the requirements
of the said customer. The installation
and the commissioning must be done
by persons authorised by Castelmac.
2.6 Safety and control systems
Door microswitch:
this shuts down fan operation in the cell
when the door is open.
General protection fuses :
these protect the full power circuit from
short circuits and any overloads.
Safety thermostat:
This cuts in in the case of overtempera-
ture due to long operating times of the
evaporator defrosting heating elements.
Safety pressure switch:
this cuts in in the case overpressure in
the refrigerating circuit
Door opening from inside if it accidental-
ly shuts
• Chamber temperature check:
this is managed by the electronic card
through the sensor inside the cell•
Temperature check at the end of defrost-
ing:
this is managed by the electronic card
through the sensor on the evaporator.
2.7 WEEE Notice
The Directive on Waste Electrical and
Electronic Equipment (WEEE), which entered
into force as European law on 13th February
2003, resulted in a major change in the treat-
ment of electrical equipment at end-of-life.
The purpose of this Directive is, as a first pri-
ority, the prevention of WEEE, and in addi-
tion, to promote the reuse, recycling and
other forms of recovery of such wastes so as
to reduce disposal.
The WEEE logo on the product or
on its box indicates that this product
must not be disposed of or dumped
with your other household waste.
You are liable to dispose of ali your
electronic or electrical waste equip-
ment by relocating over to the spec-
ified collection point for recycling of
such hazardous waste. Isolated col-
lection and proper recovery of your
electronic and electrical waste
equipment at the time of disposal
will allow us to help conserving nat-
ural resources. Moreover, proper
recycling of the electronic and elec-
trical waste equipment will ensure
safety of human health and environ-
ment. For more information about
electronic and electrical waste
equipment disposal, recovery, and
collection points, please contact
your local city centre, household
waste disposal service, shop from
where you purchased the equip-
ment, or manufacturer of the equip-
ment.