Warning:
• The unit must not be installed by the user. Ask a dealer or an authorized
technician to install the unit. If the unit is installed incorrectly, water leakage,
electric shock, or fire may result.
• This appliance is intended to be used by expert or trained users in shops, in
light industry and on farms, or for commercial use by lay persons.
• For installation work, follow the instructions in the Installation Manual and
use tools and pipe components specifically made for use with R410A refrig-
erant. The R410A refrigerant in the HFC system is pressurized 1.6 times the
pressure of usual refrigerants. If pipe components not designed for R410A
refrigerant are used and the unit is not installed correctly, the pipes may burst
and cause damage or injuries. In addition, water leakage, electric shock, or
fire may result.
• The unit must be installed according to the instructions in order to minimize
the risk of damage from earthquakes, typhoons, or strong winds. An incor-
rectly installed unit may fall down and cause damage or injuries.
• The unit must be securely installed on a structure that can sustain its weight.
If the unit is mounted on an unstable structure, it may fall down and cause
damage or injuries.
• If the air conditioner is installed in a small room, measures must be taken to
prevent the refrigerant concentration in the room from exceeding the safety
limit in the event of refrigerant leakage. Consult a dealer regarding the appro-
priate measures to prevent the allowable concentration from being exceeded.
Should the refrigerant leak and cause the concentration limit to be exceeded,
hazards due to lack of oxygen in the room may result.
• Ventilate the room if refrigerant leaks during operation. If refrigerant comes
into contact with a flame, poisonous gases will be released.
• All electric work must be performed by a qualified technician according to
local regulations and the instructions given in this manual. The units must be
powered by dedicated power lines and the correct voltage and circuit breakers
must be used. Power lines with insufficient capacity or incorrect electrical
work may result in electric shock or fire.
• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes,
to connect the refrigerant pipes. If the pipes are not connected correctly, the
unit will not be properly grounded and electric shock may result.
• Use only specified cables for wiring. The wiring connections must be made
securely with no tension applied on the terminal connections. Also, never
splice the cables for wiring (unless otherwise indicated in this document).
Failure to observe these instructions may result in overheating or a fire.
• The terminal block cover panel of the outdoor unit must be firmly attached. If
the cover panel is mounted incorrectly and dust and moisture enter the unit,
electric shock or fire may result.
• When installing or relocating, or servicing the air conditioner, use only the
specified refrigerant (R410A) to charge the refrigerant lines. Do not mix it with
any other refrigerant and do not allow air to remain in the lines.
If air is mixed with the refrigerant, then it can be the cause of abnormal high
pressure in the refrigerant line, and may result in an explosion and other
hazards.
The use of any refrigerant other than that specified for the system will cause
mechanical failure or system malfunction or unit breakdown. In the worst
case, this could lead to a serious impediment to securing product safety.
• Use only accessories authorized by Mitsubishi Electric and ask a dealer or an
authorized technician to install them. If accessories are incorrectly installed,
water leakage, electric shock, or fire may result.
• Do not alter the unit. Consult a dealer for repairs. If alterations or repairs are
not performed correctly, water leakage, electric shock, or fire may result.
• The user should never attempt to repair the unit or transfer it to another loca-
tion. If the unit is installed incorrectly, water leakage, electric shock, or fire
may result. If the air conditioner must be repaired or moved, ask a dealer or
an authorized technician.
• After installation has been completed, check for refrigerant leaks. If refriger-
ant leaks into the room and comes into contact with the flame of a heater or
portable cooking range, poisonous gases will be released.
1. Safety precautions
► Before installing the unit, make sure you read all the “Safety precau-
tions”.
► Please report to or take consent by the supply authority before connec-
tion to the system.
► Equipment complying with IEC/EN 61000-3-12
► PUMY-P·VKM series is designed for use in the residential, commercial
and light-industrial environment.
► PUMY-P·YKM series is designed as professional equipment.
Warning:
Describes precautions that must be observed to prevent danger of injury or
death to the user.
Caution:
Describes precautions that must be observed to prevent damage to the unit.
After installation work has been completed, explain the “Safety Precautions,” use, and
maintenance of the unit to the customer according to the information in the Operation
Manual and perform the test run to ensure normal operation. Both the Installation
Manual and Operation Manual must be given to the user for keeping. These manuals
must be passed on to subsequent users.
: Indicates a part which must be grounded.
Warning:
Carefully read the labels affixed to the main unit.
Confirmation of parts attached
In addition to this manual, the following parts are supplied with the outdoor unit.
They are used for grounding the S terminals of transmission terminal blocks TB3,
TB7. For details refer to “6. Electrical work”.
Grounding lead wire with a ferrite core for TB3
Caution:
• Do not vent R410A into the Atmosphere:
• R410A is a Fluorinated Greenhouse gas, covered by the Kyoto Protocol, with a Global Warming Potential (GWP)=1975.
Contents
1. Safety precautions .....................................................................................2
2. Installation location ....................................................................................4
3. Installing the outdoor unit ..........................................................................6
4. Installing the refrigerant piping ..................................................................6
5. Drainage piping work ............................................................................... 11
6. Electrical work ......................................................................................... 11
7. Test run ....................................................................................................18
<PUMY-P112-140YKM1>
<PUMY-P112-140VKM1>
Grounding lead wire (× 2)
Grounding lead wire without a ferrite core for TB7
Содержание
- Air conditioners pumy p112 p125 p140vkm1 pumy p112 p125 p140ykm1 1
- Dansk da 1
- Deutsch d 1
- English gb 1
- Español e 1
- Eγχeipiδio oδhγiωn eγkataσtaσhσ 1
- Eλληνικά gr 1
- For use with r410a 1
- Français f 1
- Installatiehandleiding 1
- Installation manual 1
- Installationshandbuch 1
- Installationsmanual 1
- Italiano i 1
- Manual de instalación 1
- Manual de instalação 1
- Manuale di installazione 1
- Manuel d installation 1
- Montaj elki tabi 1
- Nederlands nl 1
- Português p 1
- Svenska sw 1
- Türkçe tr 1
- Руководство по установке 1
- Русский ru 1
- Contents 2
- Confirmation of parts attached 2
- Safety precautions 2
- Before electric work 3
- Before installation 3
- Before installation relocation 3
- Before starting the test run 3
- Safety precautions 3
- Using r410a refrigerant air conditioners 3
- Choosing the outdoor unit installation location 4
- Connecting a pwfy unit 4
- Connection restrictions 4
- Fig 2 1 4
- Fig 2 2 4
- Indoor unit specifications 4
- Installation location 4
- Outline dimensions outdoor unit fig 2 1 4
- Refrigerant collecting pump down 4
- Refrigerant pipe 4
- Switch settings fig 2 2 4
- Test run 4
- Fig 2 10 fig 2 11 fig 2 12 5
- Fig 2 13 fig 2 14 fig 2 15 5
- Fig 2 4 5
- Fig 2 6 fig 2 5 fig 2 3 5
- Fig 2 7 5
- Fig 2 8 fig 2 9 5
- Installation location 5
- Max 00 5
- Ventilation and service space 5
- Fig 2 16 fig 2 17 6
- Fig 3 1 6
- Installation location 6
- Installing the outdoor unit 6
- Installing the refrigerant piping 6
- Precautions for devices that use r410a refrigerant 6
- Windy location installation 6
- Connection with branch box fig 4 2 7
- Connection without branch box fig 4 1 7
- Fig 4 1 7
- Fig 4 2 7
- Installing the refrigerant piping 7
- Pipe length and height difference 7
- Connection with branch box fig 4 3 8
- Connection without branch box 8
- Fig 4 3 8
- Fig 4 4 8
- Installing the refrigerant piping 8
- Selecting pipe size 8
- Connecting pipes fig 4 5 9
- Fig 4 5 9
- Fig 4 6 9
- Fig 4 7 9
- Installing the refrigerant piping 9
- Refrigerant piping fig 4 7 9
- Fig 4 10 10
- Fig 4 11 10
- Fig 4 8 10
- Fig 4 9 10
- Installing the refrigerant piping 10
- Refrigerant pipe airtight testing method 10
- Stop valve opening method 10
- Additional refrigerant charge 11
- Caution 11
- Drainage piping work 11
- Electrical work 11
- Installing the refrigerant piping 11
- Control box and connecting position of wiring fig 6 1 12
- Electrical work 12
- Example of a group operation system with multiple outdoor units shielding wires and address setting are necessary 12
- Fig 6 1 12
- Wiring transmission cables 12
- Electrical work 13
- Fig 6 2 fig 6 3 13
- Fig 6 4 13
- Electrical work 14
- Fig 6 5 14
- Fig 6 6 14
- Wiring of main power supply and equipment capacity 14
- Electrical work 15
- Electrical work 16
- Address setting 17
- Electrical work 17
- Before test run 18
- Refrigerant collecting pump down 18
- Test run 18
- Using remote controller 18
- Using sw3 in outdoor unit 18
- Данное устройство предназначено для использования специалистами или обученным персоналом в магазинах на предприятиях легкой промышленности и фермах или для коммерческого применения непрофессионалами 19
- Дренажные трубы 98 6 электрические работы 98 7 выполнение испытания 05 19
- Меры предосторожности 19
- Меры предосторожности 89 2 место монтажа 91 3 установка наружного прибора 93 4 прокладка труб хладагента 93 19
- Поставляемые приспособления 19
- Содержание 19
- Использование кондиционеров с хладагентом r410a 20
- Меры предосторожности 20
- Перед тестовым прогоном 20
- Перед установкой 20
- Перед установкой перемещением 20
- Перед электрическими работами 20
- Fig 2 1 21
- Fig 2 2 21
- Выбор места установки наружного прибора 21
- Контурные габариты наружный прибор fig 2 1 21
- Место монтажа 21
- Подключение блока pwfy 21
- Трубы хладагента 21
- Fig 2 10 fig 2 11 fig 2 12 22
- Fig 2 13 fig 2 14 fig 2 15 22
- Fig 2 4 22
- Fig 2 6 fig 2 5 fig 2 3 22
- Fig 2 7 22
- Fig 2 8 fig 2 9 22
- Вентиляция и сервисное пространство 22
- Макс 300 22
- Макс 500 22
- Место монтажа 22
- При установке нескольких наружных приборов 22
- При установке одиночного наружного прибора 22
- Fig 2 16 fig 2 17 23
- Fig 3 1 23
- Меры предосторожности для устройств в которых используется хладагент марки r410a 23
- Место монтажа 23
- Прокладка труб хладагента 23
- Установка в местах где возможен сильный ветер 23
- Установка наружного прибора 23
- Fig 4 1 24
- Fig 4 2 24
- Длина труб и разность высот fig 5 1 24
- Подключение без использования ответвительной коробки fig 4 1 24
- Подключение с использованием ответвительной коробки fig 4 2 24
- Прокладка труб хладагента 24
- Fig 4 3 25
- Fig 4 4 25
- Выбор размера труб 25
- Подключение без использования ответвительной коробки 25
- Подключение с использованием ответвительной коробки fig 4 3 25
- Прокладка труб хладагента 25
- Fig 4 5 26
- Fig 4 6 26
- Fig 4 7 26
- Прокладка труб хладагента 26
- Прокладка труб хладагента fig 4 7 26
- Соединение труб fig 4 5 26
- Fig 4 10 27
- Fig 4 11 27
- Fig 4 8 27
- Fig 4 9 27
- Метод проверки герметичности трубопровода хладагента 27
- Прокладка труб хладагента 27
- Способ открытия запорного крана 27
- Дополнительный заряд хладагента 28
- Дренажные трубы 28
- Осторожно 28
- Прокладка труб хладагента 28
- Электрические работы 28
- Fig 6 1 29
- Блок управления и положение проводки fig 6 1 29
- Пример работы заземленной системы с многочисленными внешними приборами подсоединения и провода прикреплены как необходимо 29
- Прокладка кабелей передачи 29
- Электрические работы 29
- Fig 6 2 fig 6 3 30
- Fig 6 4 30
- М не менее 1 25 мм 30
- Максимальная длина кабеля передачи кабель m net 30
- Максимальная длина через внешние приборы кабель m net 30
- Электрические работы 30
- Fig 6 5 31
- Fig 6 6 31
- Электрические работы 31
- Электропроводка для сетевого питания и характеристики оборудования 31
- Электрические работы 32
- В случае использования цепи управления a есть опасность возникновения высокого напряжения на клемме s3 вследствие конструкции электрической схемы которая не имеет электрической изоляции между линией питания и сигнальной линией связи поэтому при выполнении технического обслуживания выключите основной источник питания а также не прикасайтесь к клеммам s1 s2 s3 когда подается напряжение если изолятор необходимо будет использовать между наружным прибором и ответвительной коробкой внутренним прибором и ответвительной коробкой используйте 3 полюсный или 2 полюсный тип см рис ниже 33
- Никогда не сращивайте кабель питания или соединительный кабель внутренней или наружной ответвительной коробки в противном случае это может при вести к образованию дыма пожару или отказу связи 33
- Осторожно после использования изолятора не забудьте выключить и включить основной источник питания для перезагрузки системы в противном случае наружный прибор не сможет обнаружить ответвительную коробку коробки или внутренние приборы 33
- Предупреждение 33
- Электрические работы 33
- Установка адреса 34
- Установка адреса переключателей 34
- Электрические работы 34
- Выполнение испытания 35
- Использование sw3 в наружном блоке 35
- Использование пульта дистанционного управления 35
- Перед пробным прогоном 35
- Сбор хладагента откачка 35
- Aslı i ngilizce dir diğer dillerdeki sürümler aslının çevirisidir 38
- Attenzione 38
- Caution 38
- Cuidado 38
- Di kkat 38
- El idioma original del documento es el inglés las versiones en los demás idiomas son traducciones del original 38
- Engelsk er originalen de andre sprogversioner er oversættelser af originalen 38
- English is original the other languages versions are translation of the original 38
- Forsigtig 38
- Försiktighet 38
- Het engels is het origineel de andere taalversies zijn vertalingen van het origineel 38
- O idioma original é o inglês as versões em outros idiomas são traduções do idioma original 38
- Precaution 38
- Voorzichtig 38
- Vorsicht 38
- Η γλώσσα του πρωτοτύπου είναι η αγγλική οι εκδόσεις άλλων γλωσσών είναι μεταφράσεις του πρωτοτύπου 38
- Προσοχη 38
- Bh79d391h03 printed in japan 39
- Please be sure to put the contact address telephone number on this manual before handing it to the customer 39
Похожие устройства
- Mitsubishi Electric PUMY-P112VKM Сертификат
- Mitsubishi Electric PUHY-P350YKB-A1.TH Инструкция по установке
- Mitsubishi Electric PUHY-P350YKB-A1.TH Сертификат
- Mitsubishi Electric PUMY-P140YKM Инструкция по установке
- Mitsubishi Electric PUMY-P140YKM Сертификат
- Mitsubishi Electric PUHY-P400YKB-A1.TH Инструкция по установке
- Mitsubishi Electric PUHY-P400YKB-A1.TH Сертификат
- Mitsubishi Electric PUMY-P112YKM Инструкция по установке
- Mitsubishi Electric PUMY-P112YKM Сертификат
- Mitsubishi Electric PUMY-P200YKM Инструкция по установке
- Mitsubishi Electric PUMY-P200YKM Сертификат
- Victoria Arduino Venus Bar 2 Gr V медь Инструкция по эксплуатации
- Mitsubishi Electric PUHY-EP200YLM-A Инструкция по установке
- Mitsubishi Electric PUHY-EP200YLM-A Сертификат
- Mitsubishi Electric PUHY-EP300YLM-A Инструкция по установке
- Mitsubishi Electric PUHY-EP300YLM-A Сертификат
- Mitsubishi Electric PUHY-P200YKB-A1.TH Инструкция по установке
- Mitsubishi Electric PUHY-P200YKB-A1.TH Сертификат
- Mitsubishi Electric PUHY-P300YKB-A1.TH Инструкция по установке
- Mitsubishi Electric PUHY-P300YKB-A1.TH Сертификат