AEG SDH 200/5,7 Twin [24/60] Installation for contractors

AEG SDH 150/12.5 Twin [24/60] Installation for contractors
24 
Installation - for contractors
 
26_07_29_0093
1
2
3 4 5 6
8
9
10
7
11
1  Electronic room controller
2  Protective pipe with sensor sleeve for temperature sensor
3  Floor covering
4  Floor adhesive
5  Heating mat (screed centre)
6  Cement screed (6 to 10 cm subject to storage volume of the walls surrounding the room and the charge time)
7  Edge insulation strips
8  Damp proof membrane 0.2 (0.5) mm PE or bitumen paper 250 g
9  Insulation layer, for example mineral fibre insulation
10 Damp proof membrane (only when ground below), 0.5 mm PE or bitumen paper 500 g
11 Unfinished concrete or ground
» For a short heat-up time, select as thin a screed thickness as possible whilst still complying with the minimum thickness 
specified in your region.
 
!

» Prior to laying the mats, compare the structural conditions with the application drawings. Clarify any deviations with the 
site management. These deviations must not impede the heating mats.
» Lay the heating mats in accordance with the application drawings so that the cold conductor connections are near the 
junction box.
» Connect the existing cable screen to the earth conductor.
» The area specified to be heated in the application drawings will be achieved if you cut through the heating mat grid at 
the reversing points provided. At the cutting point, bend over the heating conductor and lay the next strip parallel to 
the first one. If required, repeat this process.
»  Check the resistance or the insulation value of the heating mats. The insulation resistance of the 
heating mats with screen in the delivered condition is 10 megohm.