Airwell AQH 130 [14/28] Performance data in cooling mode hfc 407c continued

Airwell AQH 130 [14/28] Performance data in cooling mode hfc 407c continued
Page 14
Performance data in cooling mode - HFC 407C (continued)
LCWT
(°C) Pf Pabs Pf Pabs Pf Pabs Pf Pabs Pf Pabs Pf Pabs Pf Pabs
5
87.6 28.3 84.7 30.3 83.4 31.2 81.4 32.5 75.4 35.8 71.7 37.9 68.1 40.2
6
90.2 28.6 87.2 30.7 85.8 31.5 83.8 32.8 77.6 36.2 73.9 38.3 70.1 40.6
7
92.9 28.9 89.8 31.0 88.5 31.8
86.4 33.2
80.0 36.6 76.2 38.7 72.4 41.0
8
95.5 29.3 92.5 31.4 91.1 32.2 88.9 33.6 82.4 37.0 78.5 39.1 74.5 41.4
9
98.4 29.6 95.2 31.7 93.7 32.6 91.5 33.8 84.8 37.3 80.8 39.5 76.8 41.8
10
101.1 29.9 97.9 32.1 96.4 32.9 94.2 34.2 87.3 37.7 83.1 39.9 79.0 42.2
5
99.3 32.3 96.1 34.7 94.7 35.7 92.4 37.2 85.4 40.9 81.3 43.3 77.1 45.8
6
102.3 32.7 98.9 35.1 97.5 36.1 95.1 37.5 88.0 41.3 83.7 43.7 79.3 46.2
7
105.2 33.1 101.9 35.5 100.4 36.4
98.0 37.9
90.6 41.7 86.2 44.2 81.7 46.7
8
108.3 33.5 104.8 36.0 103.3 36.8 100.8 38.4 93.3 42.2 88.8 44.6 84.1 47.1
9
111.4 33.9 107.7 36.3 106.2 37.3 103.6 38.8 95.9 42.6 91.2 45.0 86.7 47.4
10
114.4 34.3 110.7 36.7 109.1 37.7 106.6 39.2 98.6 43.0 93.8 45.4 89.0 47.9
5
115.2 36.0 111.7 38.5 110.0 39.5 107.6 41.1 99.8 45.3 95.2 47.9 90.5 50.6
6
118.7 36.4 114.9 39.0 113.3 40.0 110.8 41.5 102.9 45.7 98.1 48.3 93.3 51.2
7
122.1 36.9 118.3 39.4 116.7 40.5
112.0 42.0
106.1 46.2 101.1 48.9 96.2 51.7
8
125.6 37.3 121.7 39.9 120.1 41.0 117.4 42.6 109.2 46.7 104.1 49.4 99.1 52.2
9
129.2 37.7 125.2 40.4 123.5 41.4 120.9 43.1 112.4 47.3 107.2 50.0 102.1 52.7
10
132.8 38.2 128.8 40.9 127.1 41.9 124.3 43.5 115.5 47.9 110.3 50.6 105.0 53.3
5
123.4 39.7 119.8 42.6 118.1 43.8 115.4 45.5 107.2 50.0 102.1 52.8 97.1 55.8
6
127.1 40.2 123.2 43.1 121.5 44.3 118.9 46.0 110.3 50.6 105.1 53.4 99.9 56.4
7
130.6 40.7 126.8 43.7 125.1 44.8
122.2 46.6
113.5 51.1 108.2 54.0 102.8 56.9
8
134.3 41.3 130.4 44.2 128.5 45.4 125.7 47.1 116.7 51.7 111.3 54.6 105.6 57.6
9
138.1 41.8 134.0 44.8 132.1 46.0 129.2 47.7 119.9 52.3 114.3 55.2 108.7 58.2
10
141.8 42.4 137.6 45.4 135.8 46.5 132.7 48.3 123.2 53.0 117.4 55.8 111.6 58.9
5
131.1 40.3 127.3 43.3 125.6 44.4 122.9 46.1 114.0 50.6 108.7 53.4 103.4 56.4
6
135.1 40.8 131.2 43.8 129.4 44.9 126.6 46.7 117.7 51.2 112.1 54.0 106.6 57.0
7
139.3 41.3 135.2 44.3 133.4 45.5
131.0 47.0
121.2 51.7 115.5 54.6 109.8 57.6
8
143.4 41.8 139.3 44.8 137.3 45.9 134.3 47.7 124.8 52.3 118.9 55.2 113.1 58.2
9
147.7 42.4 143.4 45.3 141.5 46.5 138.3 48.3 128.4 52.8 122.5 55.7 116.4 58.7
10
152.0 42.9 147.5 45.8 145.5 47.0 142.4 48.7 132.2 53.4 126.0 56.4 119.7 59.3
AQH
sizes
Outdoor air temperature (°C)
25 30 32 35 40 43 46
130
90
100
110
120
All the cooling capacity and power consumption values are expressed in kW.
The values indicated in bold are based on Eurovent conditions (chilled water inlet / outlet temperatures of 12 / 7 °C and an outdoor air
temperature of + 35 °C).
The power consumption values stated in the table include compressors and fans in operation.
LCWT: Leaving Chilled Water Temperature
Pf : Cooling capacity
Pabs : Power consumption