Airwell RWC 360 [10/16] Electrical data rwc rwr

Airwell RWC 240 [10/16] Electrical data rwc rwr
Page 10
Electrical Data - RWC/RWR
MODELS 170 200 240 280 320 360
UNIT
Nominal supply voltage V(%)-Ph-Hz 400(±10%)/3/50
Max. power input kW 66 77 89 112 130 147
Nominal current A 87 97 107 127 149 171
Max. current FLA A 111 131 151 190 219 248
Max. starting current LRA A 281 355 375 415 477 506
COMPRESSORS
Quantity 4 4 4 4 4 4
Max. power input kW 16.4 x 4
16.4 x 3 + 28.1
(16.4+28.1)x2 28.1 x 4 (28.1+36.7)x2 36.7x4
Max. current FLA A 28 x 4 28 x 3 +48 (28+48)x2 48 x 4 (48+62)x2 62x4
Max. starting current LRA A 198 x 4 198 x 3 + 272 (198+272)x2 272 x 4 (272+320)x2 320x4
Crankcase heater W 70 70 70 150 150 150
RWC/RWR
Frequencies (Hz)
Lw
global
dB(A)
Lp
global
dB(A) *
125 250 500 1000 2000 4000 8000
170 61.1 76.8 77.9 76.3 74.8 67.4 55.4 81.0 63.9
200 62.1 77.8 78.9 77.3 75.8 68.4 56.4 82.0 64.9
240 62.1 77.8 78.9 77.3 75.8 68.4 56.4 82.0 64.9
280 64.1 79.8 80.9 79.3 77.8 70.4 58.4 84.0 66.9
320 65.1 80.8 81.9 80.3 78.8 71.4 59.4 85.0 67.9
360 66.1 81.8 82.9 81.3 79.8 72.4 60.4 86.0 68.9
RWC/RWR
Frequencies (Hz)
Lw
global
dB(A)
Lp
global
dB(A) *
125 250 500 1000 2000 4000 8000
170 57.1 72.8 73.9 72.3 70.8 63.4 51.4 77.0 59.9
200 58.1 73.8 74.9 73.3 71.8 64.4 52.4 78.0 60.9
240 58.1 73.8 74.9 73.3 71.8 64.4 52.4 78.0 60.9
280 60.1 75.8 76.9 75.3 73.8 66.4 54.4 80.0 62.9
320 61.1 76.8 77.9 76.3 74.8 67.4 55.4 81.0 63.9
360 62.1 77.8 78.9 77.3 75.8 68.4 56.4 82.0 64.9
(*) Sound pressure levels given at 1 meter from the unit according to ISO 3744 standard. Tolerance : ±2 dB(A).
(*) Sound pressure levels given at 1 meter from the unit according to ISO 3744 standard. Tolerance : ±2 dB(A).
Models RWC/RWR 170 to 360 - Standard version (without acoustic jacket)
Models RWC/RWR 170 to 360 - Low noise version (with acoustic jacket)
Sound Data
Скачать