Airwell RWC 360 [9/16] Physical data rwr 170 to 360

Airwell RWC 360 [9/16] Physical data rwr 170 to 360
Page 9
Physical Data - RWR 170 to 360
RWR MODELS 170 200 240 280 320 360
Cooling capacity (1) kW 160.8 186.5 210.6 263.6 283.7 312.3
Power input
(1) kW 45.8 52.6 56.8 73.0 81.7 90.5
Heat rejection kW 205.7 238.4 267.4 336.6 365.4 402.8
Number of refrigerant circuits 2 2 2 2 2 2
Number of capacity steps 4 4 4 4 4 4
Power supply
V(%)-Ph-Hz 400 (±10%)/3/50
Starting type Direct
COMPRESSORS
Number 4 4 4 4 4 4
Type
Scroll
EVAPORATORS
Type
Shell and tube heat exchanger
Number 1 1 1 1 1 1
Nominal water flow l/s 7.3 8.5 9.6 12 13 14.2
Nominal water pressure drop kPa 32 43 19 30 35 42
Water volume each
l 63 63 53 53 53 53
EVAPORATOR HYDRAULIC CONNECTIONS
Type
Victaulic
Inlet diameter 4" 4" 4" 4" 4" 4"
Outlet diameter 4" 4" 4" 4" 4" 4"
REFRIGERANT CONNECTIONS
Type To be brazed
Discharge line diameter 1" 3/8 1" 3/8 1" 3/8 1" 3/8 1" 3/8 1" 3/8
Liquid line diameter 7/8" 7/8" 7/8" 7/8" 7/8" 7/8"
WEIGHT
Shipping kg 1080 1122 1216 1313 1327 1341
Operating kg 1143 1185 1269 1366 1380 1394
DIMENSIONS
Length
mm 2200 2200 2200 2200 2200 2200
Width mm 800 800 800 800 800 800
Height mm 1820 1820 1820 1820 1820 1820
SOUND LEVELS (WITHOUT ACOUSTIC JACKET)
Sound power levels dB(A) 81 82 82 84 85 86
Sound pressure levels (2) dB(A) 63.9 64.9 64.9 66.9 67.9 68.9
SOUND LEVELS (WITH ACOUSTIC JACKET)
Sound power levels dB(A) 77 78 78 80 81 82
Sound pressure levels (2) dB(A) 59.9 60.9 60.9 62.9 63.9 64.9
(1) At conditions : evaporator water temperature of 12/7 °C and condensing temperature of 45 °C.
(2) Sound pressure levels given at 1 meter from the unit in free field.