Operating Limits
Correction Factors
RWC / RWR
170 200 240 280 320 360
Min. Max. Min. Max. Min. Max. Min. Max. Min. Max. Min. Max.
Evaporator
Liquid leaving
temperature
Water
°C +6 to +15
Water with glycol
°C -5 to +15
Water temp. difference
°K 3 to 7
Water flow
(1) l/s 5.5 12.8 6.4 14.9 17.2 16.8 9.0 26.0 9.7 23.0 10.7 25.0
Pressure drop (1) kPa
18 99 24 133 11 59 17 93 20 107 24 130
Max. working pressure - Water side
bar 10
Condenser (2)
Water leaving temperature
°C +30 to +50
Water flow
(1) l/s 3.5 8.2 4.1 9.5 4.6 10.6 5.7 13.4 6.2 14.5 6.9 16.0
Pressure drop
(1) kPa 14 75 19 102 15 81 24 128 17 94 21 115
Max. working pressure - Water side
bar 10
(1) Total unit flow rate and pressure drop are given.
(2) Only for RWC models.
EVAPORATOR CONDENSER
Fouling factor
(m
2
.°C/kW)
Cooling
capacity
Power
input
Fouling factor
(m
2
.°C/kW)
Cooling
capacity
Power
input
0.044 1.000 1.000 0.044 1.000 1.000
0.088 0.987 0.995 0.088 0.987 1.023
0.176 0.964 0.985 0.176 0.955 1.068
0.352 0.915 0.962 0.352 0.910 1.135
Fouling factors