Generac SG32/PG29 [30/36] Установка

Generac SG28/PG25 [30/36] Установка
28
Установка
Рисунок 1.23 — Типовые пользовательские подключения в пользовательском модуле высоковольтных соединений.
L2
TB2-4Y219
23
SUPPLIED WITH
3-WIRE
GROUNDED
PLUG TO BE
CONNECTED
BY OTHERS
TB4 OR
LOAD CENTER
TB4 OR
LOAD CENTER
SUPPLIED WITH
3-WIRE
GROUNDED
PLUG.
TYPICALLY
PLUG IS
REMOVED
BY THE
INSTALLER
AND WIRES
ARE
TERMINATED IN
JUNCTION BOX
NOTE:
FOR FIELD WIRING TO CUSTOMER CONNECTIONS
(TERMINAL STRIPS AND RELAY BOARD)
MAXIMUM WIRE SIZE: #14 AWG
RECOMMENDED TIGHTENING TORQUE: 12 LB-IN
OPTIONAL
RR-6NO24
RUN RELAY
RR-5NC26
COM25 RR-8
3 NC1
2 COM1
RR-4
RR-1
1 NO1 RR-3
TB5
Y
X
NO1 TB5-1X
NC1
NC2
TB5-3X
TB5-6X
5
6
4
TB5-5XCOM2
8
NO2
7
0
TB5-4X
TB2-6Y
COM1
1
TB5-2X
OIL HEATER
(SHIPPED LOOSE)
COMMON OPTIONS
FOR
CUSTOMER
CONNECTIONS
(BATTERY
WARMER AND
OIL HEATER)
GND
BATTERY WARMER
(SHIPPED LOOSE)
JUNCTION BOX
THERMOSTAT
L
N
GREEN
WHITE
BLACK
BLOCK HEATER
(VERTICAL MOUNT)
(HORIZONTAL MOUNT)
BLOCK HEATER
OPTIONAL
STATOR CAN HEATER
COMPONENTS LOCATED IN HIGH VOLTAGE CUSTOMER CONNECTION MODULE
3
TB4 OR
LOAD CENTER
NOTE:
FOR FIELD WIRING TO CUSTOMER CONNECTIONS
(TERMINAL STRIP)
MAXIMUM WIRE SIZE: #10 AWG
RECOMMENDED TIGHTENING TORQUE: 14 LB-IN
RUN RELAY
14
GND
13
12
120 VAC OR 240 VAC
ACCESSORY POWER
(FROM CUSTOMER UTILITY SUPPLY)
BCC-3 GND
L2
11
10
9
8
BCC-2 N
7
N
6
4
5
TB4
BCC-1 L1
2
L1
1
YX
125A
120/240 VAC
UTILITY SUPPLY
(BY CUSTOMER)
VERIFY COMPONENT
RATINGS FOR PROPER
SUPPLY VOLTAGE
TO BE PROVIDED.
GND
GND
HOT
WHITE
LOAD CENTER
RECEPTACLE
TB4 OR
HOT
L1
240V
OUTPUT
LOAD
GFCI
INPUT
LINE
N
WHITE
HOT
L1
HOT
GND
GND
LOAD CENTER
GND
L2
OR
L1
N
L1
GND
NOTE: ALL WIRES ON THIS
PAGE ARE 600V RATED
14
14
14