Servicing the generator TEC60, TEC60LPG
22
10.2 Preparing maintenance work
!
Open the generator flap.
Switch the generator to no function with the main switch (fig. 2 1, page 3).
Disconnect the positive terminal of the supply battery.
For maintenance work, you can take the generator out (fig. 5, page 5):
!
Undo the fastening screws (1).
Remove the mounting plate (2) with the generator from the housing (3).
Interval Inspection/maintenance
In the first month
or after 20 hours.
Change the oil.
Check the air filter (chapter “Servicing the air filter” on page 24).
Every 3 months or
after 50 hours.
Check the air filter (chapter “Servicing the air filter” on page 24).
Every 6 months or
after 100 hours.
Change the oil.
Check the spark plug (chapter “Servicing the spark plugs” on
page 25).
Once a year or
every 300 hours
Check the valves.
Check the fuel tank (only TEC 60) and fuel filter.
Check the vibration damper.
Every two years Check the petrol supply lines (TEC60) and gas supply lines
(TEC60LPG).
CAUTION!
Note the following for all maintenance work:
The generator must not be running.
All the parts must be cooled down.
WARNING!
The mounting plate with generator is very heavy (> 70 kg) and could fall
out the housing if you take it out too far.