TEC60, TEC60LPG Troubleshooting
27
The generator
tends to go off.
Too much oil in the engine.
Drain the oil.
Load is over 6,2 kW.
Switch off the consumers.
Only TEC60:
Carburettor is not receiving any petrol.
Clean the carburettor.
Air intake is blocked.
Check the air filter (see chapter
“Servicing the air filter” on
page 24).
Inverter is damaged.
Contact an authorised workshop.
Electromagnet (inverter) is blocked.
Air filter is dirty.
The generator is
running but does
not supply any volt-
age.
Inverter is damaged.
Check the output wiring connec-
tion
Contact an authorised workshop.
RPM too low.
The generator
starts up very fast
and then the
“GENERATOR
ALERT” message
appears.
The stepper motor is faulty or the cable is
disconnected.
Contact an authorised workshop.
The generated
voltage is unstable.
Inverter is damaged.
Contact an authorised workshop.
Fault Cause Remedy
TEC60-TEC60LPG-O-16s.book Seite 27 Donnerstag, 14. Juli 2016 7:05 19