Parameter listing and descriptions 177
ACH550-02 User's Manual
0133 PID 2 DEVIATION unit and scale defined
by par. 4206 and 4207
Difference between the PID2 controller reference value and actual
value
Units and scale defined by PID parameters
0134 COMM RO WORD 0…65535
Free data location that can be written from the serial link
Used for relay output control
See parameter 1401.
0135 COMM VALUE 1 -32768…+32767
Free data location that can be written from the serial link
0136 COMM VALUE 2 -32768…+32767
Free data location that can be written from the serial link
0137 PROCESS VAR 1 -
Process variable 1
Defined by parameters in Group 34: PANEL DISPLAY
0138 PROCESS VAR 2 -
Process variable 2
Defined by parameters in Group 34: PANEL DISPLAY
0139 PROCESS VAR 3 -
Process variable 3
Defined by parameters in Group 34: PANEL DISPLAY
0140 RUN TIME 0.00…499.99 kh
Drive’s accumulated running time in thousands of hours (kh).
Cannot be reset.
0141 MWH COUNTER 0…65535 MWh
Drive’s accumulated power consumption in megawatt hours.
The counter value is accumulated till it reaches 65535 after which the
counter rolls over and starts again from 0.
Cannot be reset.
0142 REVOLUTION CNTR 0…65535 Mrev
Motor’s accumulated revolutions in millions of revolutions.
Can be reset by pressing the UP and DOWN keys simultaneously
when in the Parameters mode.
0143 DRIVE ON TIME HI 0…65535 days
Drive’s accumulated power on-time in days.
Cannot be reset.
0144 DRIVE ON TIME LO 00.00.00…23:59:58
Drive’s accumulated power on-time in 2 second ticks (30 ticks = 60
seconds).
Shown in format hh.mm.ss.
Cannot be reset.