398 Technical data
ACH550-02 User’s Manual
Input power (mains) cables, fuses and circuit breakers
With high power installations, the same power rules are valid for
supply and motor cables. A symmetrical 3-phase cable with
concentric shield is recommended. This is the praxis in industrial
installations and high power building installations. The
dimension of the shield has to be at least 50% of the phase
conductor. If not, a separate earth/PE conductor has to be used.
Dimension the cables and fuses in accordance with the input
current. Always pay attention to local codes when sizing the
cables and fuses.
The input power connectors are at the bottom of the drive. Input
power cable routing must be done so that the distance from the
sides of the drive is at least 20 cm (8 in) to avoid excessive
radiation to the input power cable. In case of shielded cable,
twist the cable screen wires together into a bundle (pigtail) not
longer than five times its width and connect to the PE terminal of
the drive (or PE terminal of input filter, if present).
Line current harmonics
The current harmonic levels under rated load conditions are
available on request.
Fuses
Branch circuit protection must be provided by the end-user,
sized per national and local electric codes. Recommendations
for fuses for short-circuit protection on the input cable and the
drive are given in this section.
Verify that the fuse operates rapidly enough by checking that
the short-circuit current of the installation is at least the
minimum short-circuit current given in the table below. The
short-circuit current of the installation can be calculated as
follows: