ABB ACH550-02-602A-4 [196/454] Parameter listing and descriptions

ABB ACH550-02-645A-4 [196/454] Parameter listing and descriptions
192 Parameter listing and descriptions
ACH550-02 User's Manual
4 = AI2/JOYST – Defines analogue input 2 (AI2), configured for joystick
operation, as the reference source.
• See above (
AI1/JOYST) description.
5 =
DI3U,4D(R) – Defines digital inputs as the speed reference source
(motor potentiometer control).
• Digital input
DI3 increases the speed (the U stands for “up”).
• Digital input
DI4 decreases the speed (the D stands for “down”).
• A Stop command resets the reference to zero (the
R stands for
“reset”).
• Parameter 2205
ACCELER TIME 2 controls the reference signal’s rate
of change.
6 =
DI3U,4D – Same as above (DI3U,4D(R)), except:
• A Stop command does not reset the reference to zero. The
reference is stored.
• When the drive restarts, the motor ramps up (at the selected
acceleration rate) to the stored reference.
7 =
DI5U,6D – Same as above (DI3U,4D), except that DI5 and DI6 are the
digital inputs used.
8 =
COMM – Defines the fieldbus as the reference source.
9 =
COMM+AI1 – Defines a fieldbus and analogue input 1 (AI1)
combination as the reference source. See Analogue input reference
correction on page 193.
10 =
COMM
*
AI1 – Defines a fieldbus and analogue input 1 (AI1)
combination as the reference source. See Analogue input reference
correction on page 193.
11 =
DI3U,4D(RNC) – Same as DI3U,4D(R) above, except that:
• Changing the control source (
EXT1 to EXT2, EXT2 to EXT1, LOC to
REM) does not copy the reference.
12 =
DI3U,4D(NC) – Same as DI3U,4D above, except that:
• Changing the control source (
EXT1 to EXT2, EXT2 to EXT1, LOC to
REM) does not copy the reference.
13 =
DI5U,6D(NC) – Same as DI3U,4D above, except that:
• Changing the control source (
EXT1 to EXT2, EXT2 to EXT1, LOC to
REM) does not copy the reference.
14 =
AI1+AI2 – Defines an analogue input 1 (AI1) and analogue input 2
(
AI2) combination as the reference source. See Analogue input
reference correction on page 193.
15 =
AI1
*
AI2 – Defines an analogue input 1 (AI1) and analogue input 2
(
AI2) combination as the reference source. See Analogue input
reference correction on page 193.
16 =
AI1-AI2 – Defines an analogue input 1 (AI1) and analogue input 2
(
AI2) combination as the reference source. See Analogue input
reference correction on page 193.
17 =
AI1/AI2 – Defines an analogue input 1 (AI1) and analogue input 2
(
AI2) combination as the reference source. See Analogue input
reference correction on page 193.
Code Description Range