Daikin EWAD300MBYNN [17/452] Oil type

Daikin EWAD170MBYNN [17/452] Oil type
ESIE 05-07 General Outline
Part 1 – System Outline 1–5
3
1
4
5
Notes 1. Nominal cooling capacity at Eurovent conditions: Evaporator 12°C/7°C; ambient 35°C
2. Nominal cooling power input at Eurovent conditions: Evaporator 12°C/7°C; ambient 35°C
3. Minimum required watervolume for standard thermostat setting and at nominal conditions.
4. Piping connections are delivered with victaulic joint and counterpipe for welding.
5. Dimension values between brackets include installation space of delivered filter.
Refrigerant circuit
Refrigerant
type
R407C
Refrigerant
charge
27 kg 39 kg
42 kg
58 kg 84 kg 84 kg 128 kg 129 kg 130 kg
Refrigerant
control
Thermostatic expansion valve
Oil type Idemitsu FVC 68D
Oil charge
volume
5.5 l 7.5 l
10 l
2 x 7.5 l 7.5+10 l 2x10 l
No. of cir-
cuits
1 2
Dimensions
(h x w (5) x
d (5))
2250 x 2346 (2700) x 2238 mm 2250 x 4280 (4495) x 2238 mm 2250 x 5901 x 2238 (2653) mm
Weight
Machine
weight
1417 kg 1571 kg 1660 kg 2203 kg 2583 kg 2633 kg 4865 kg 4988 kg 5111 kg
Operation
weight
1425 kg 1584 kg 1676 kg 2223 kg 2610 kg 2667 kg 4939 kg 5069 kg 5199 kg
Casing
Colour
Ivory white / Munsell code 5Y7.5/1 / ± RAL 7044
Material
Polyester coated galvanised steel plate
Sound
power
leve
91 dBA 96 dBA 97 dBA 99 dBA 100 dBA 101 dBA
Safety
devices
Q Double PED approved high pressure switches
Q Low pressure protection
Q Pressure relief valve on condenser
Q Compressor motor thermal protector
Q Compressor motor overcurrent relay
Q Discharge temperature controller
Q Freeze up protection
Q Recycling and quard timer
Q Reverse phase protector/flow switch
Model
EWAP
110MBYNN
EWAP
140MBYNN
EWAP
160MBYNN
EWAP
200MBYNN
EWAP
280MBYNN
EWAP
340MBYNN
EWAP
400MBYNN
EWAP
460MBYNN
EWAP
540MBYNN
ESIE05-07.book Page 5 Wednesday, October 11, 2006 10:42 AM

Содержание