General Outline ESIE 05-07
1–26 Part 1 – System Outline
3
11
4
5
1.14 Electrical Specifications: EWTP110~540MBYNN
Electrical
specifications
The table below contains the electrical specifications.
Model
EWTP
110MBYNN
EWTP
140MBYNN
EWTP
160MBYNN
EWTP
200MBYNN
EWTP
280MBYNN
EWTP
340MBYNN
EWTP
400MBYNN
EWTP
460MBYNN
EWTP
540MBYNN
Power supply
Phase
3N~
Frequency
50 Hz
Voltage
400 V
Voltage
tolerance
±10 %
Unit
Starting current
158 A 193 A 248 A 316 A 440 A 248 A 248/316 A 316 A
Nominal running
current cooling
70A 84A 104A 128A 180A 226A 258A 316A 373A
Max. running
current
95 A 120 A 135 A 168 A 232 A 288 A 342 A 396 A 452 A
Recommended
fuses
3 x 125gL A 3 x 160gL A 3 x 200gL A 3 x 250gL A 3 x 355gL A std: 2 x
(3x250gl)
op52: 3x400gL
std: (3x250) x
(3x300) gl
op52:
3x425gL
std: 2 x
(3x300gl)
op52:
3x500gL
Fans
Nominal running
current
4x1.9 A 4x3.1 A 8x1.9 A 8x3.1 A 12x3.1 A
Maximum
running current
4x1.9 A 4x3.1 A 8x1.9 A 8x3.1 A 12x3.1 A
Starting current
- DOL
9.5 A per fan - 6 sec
Compressor
Phase
3~
Voltage
400+/-10% V
Starting current
= Starting current of the unit
Nom. running
current
62 A 70 A 90 A 112 A 155 A 201 A 2 x 111 A 111 + 168 A 2 x 168 A
Max. running
current
87 A 106 A 121 A 152 A 206 A 262 A 2x152 A 152 + 206 A 2 x 206 A
Starting method
Star-Delta
Recommended
fuses
Factory installed
Control circuit
Phase
1~
Voltage 230/24 V AC (supplied by factory installed transformers)
Recommanded
fuses
Factory installed
Crankcase
heater (E1/2HC)
1 x (150 W -0.65 A) 2 x (150 W - 0.65 A)
ESIE05-07.book Page 26 Wednesday, October 11, 2006 10:42 AM