Test Run and Operation Data ESIE05-07
4–20 Part 4 – Commissioning and Test Run
3
1
4
5
2.3 Test Run and Operation Data for EWAD120~340MBYNN
Pressures The table below contains the measurable pressures.
Temperatures The table below contains the measurable temperatures.
Voltages The table below contains the measurable voltages.
Currents The table below contains the currents and used fuses.
Recommended fuses according to IEC standard 269-2: gL/gG (aM also admitted)
(F1U, F2U, F3U = gL/gG)
Measurement Value
Suction pressure
depending on working conditions
Discharge pressure
Maximum water pressure 10 bar
Measurement Value
Leaving water temperature
P Standard: 4 – 16°C
P With glycol: -10 – 16°C
Outdoor temperature -15 – 43°C
Temperature difference at the air side 10 – 15°C
Temperature difference at the water side 3 – 8°C
Discharge temperature 80 – 120°C
Approach temperature
(evap leaving water temp - sat. temp)
5 – 8°C (for MOW of 4°C)
for glycol units this can be > 8°C
Measurement Value
Power supply voltage Within ± 10% of the rated voltage
Phase imbalance Within ± 2% of the rated voltage
Control circuit voltage 230 V AC for main electromagnetic switches
24 V DC for the controllers
Unit Nominal current Maximum current Fuses
EWAD120MBYNN 60 A 76 A Factory installed
EWAD150MBYNN 75 A 89 A
EWAD170MBYNN 97 A 128 A
EWAD240MBYNN 2 x 60 A 2 x 76 A
EWAD300MBYNN 2 x 75 A 2 x 89 A
EWAD340MBYNN 2 x 97 A 2 x 128 A
ESIE05-07.book Page 20 Wednesday, October 11, 2006 10:42 AM