Daikin EWAD300MBYNN [19/452] Esie 05 07 general outline

Daikin EWAP280MBYNN [19/452] Esie 05 07 general outline
ESIE 05-07 General Outline
Part 1 – System Outline 1–7
3
1
4
5
Notes 1. Nominal cooling capacity at Eurovent conditions: Evaporator 12°C/7°C; ambient 35°C.
2. Nominal cooling power input at Eurovent conditions: Evaporator 12°C/7°C; ambient 35°C.
3. Minimum required watervolume for an thermostat difference between compressor ON and OFF of
2.2°C and at nominal operating conditions.
4. Piping connections are delivered with victaulic joint and counterpipe for welding.
Refrigerant circuit
Refrigerant
type
R134a
Refrigerant
charge
26 kg 37 kg
42 kg
60 kg 82 kg 88 kg
Refrigerant
control
Thermostatic expansion valve
Oil type Idemitsu FVC 68D
Oil charge
volume
7.5 l 10 l 2x7.5 l
2x10 l 2x10 l
No. of cir-
cuits
12
Dimensions
(h x w x d)
2221 x 3973 x 1109 mm 2250 x 4280 x 2238 mm
Weight
Machine
weight
1391 kg 1600 kg 1705 kg 2710 kg 3210 kg 3260 kg
Operation
weight
1441 kg 1663 kg 1768 kg 2790 kg 3340 kg 3390 kg
Casing
Colour
Ivory white / Munsell code 5Y7.5/1 / ± RAL 7044
Material
Polyester coated galvanised steel plate
Sound
power
level
87 dBA 94 dBA 92 dBA 90 dBA 97 dBA 95 dBA
Safety
devices
Q Double PED approved high pressure switches
Q Low pressure protection
Q Pressure relief valve
Q Compressor motor thermal protector
Q Compressor motor overcurrent relay
Q Discharge temperature controller
Q Freeze up protection
Q Recycling and quard timer
Q Reverse phase protector/flow switch
Model
EWAD
120MBYNN
EWAD
150MBYNN
EWAD
170MBYNN
EWAD
240MBYNN
EWAD
300MBYNN
EWAD
340MBYNN
ESIE05-07.book Page 7 Wednesday, October 11, 2006 10:42 AM

Содержание

Скачать