Daikin EWAD300MBYNN [29/452] Starting current

Daikin EWAP400MBYN [29/452] Starting current
ESIE 05-07 General Outline
Part 1 – System Outline 1–17
3
1
4
5
1.9 Electrical Specifications: EWAP110~540MBYNN
Electrical
specifications
The table below contains the electrical specifications.
Model
EWAP
110MBYNN
EWAP
140MBYNN
EWAP
160MBYNN
EWAP
200MBYNN
EWAP
280MBYNN
EWAP
340MBYNN
EWAP
400MBYNN
EWAP
460MBYNN
EWAP
540MBYNN
Power supply
Phase
3N~
Frequency
50 Hz
Voltage
400 V
Voltage
tolerance
±10 %
Unit
Starting current
158 A 193 A 248 A 316 A 440 A 248 A 248/316 A 316 A
Nominal running
current
70 A 84 A 104 A 128 A 180 A 226 A 258 A 316 A 373 A
Max. running
current
95 A 120 A 135 A 168 A 232 A 288 A 342 A 396 A 452 A
Recommended
fuses
(1)
3 x 125gL A 3 x 160gL A 3 x 200gL A 3 x 250gL A 3 x 355gL A std:
6 x 250 gL)
op52 :
3 x 400gL
std:
6 x 250 gL) +
(3 x 300) gl
op52 :
3 x 425gL
std:
6x 300gL)
op52 :
3 x 500gL
Fans
Phase
1~
Voltage
230 V
Max. running
current
4 x1.9 A 4 x3.1 A 8 x 1.9 A 8 x 3.1 A 12 x 3.1
Compressor
Phase
3~
Voltage
400+/-10% V
Starting current
= Starting current of the unit
Nom. running
current
62 A 70 A 90 A 112 A 155 A 201 A 2 x 111 A 111 + 168 A 2 x 168 A
Max. running
current
87 A 106 A 121 A 152 A 206 A 262 A 2 x 152 A 152 + 206 A 2 x 206 A
Starting method
Star-Delta
Control circuit
Phase
1~
Voltage 230/24 V AC (supplied by factory installed transformers)
Recommanded
fuses
Factory installed
Crankcase
heater (E1/2HC)
1 x (150 W -0.65 A) 2 x (150 W - 0.65 A)
Liquid line
solenoid valves
(Y15..16S/
Y25..26S)
2 x (16.1 VA -70 mA) inrush current = 130 mA 4 x (16.1 VA -70 mA) inrush
current = 130 mA
ESIE05-07.book Page 17 Wednesday, October 11, 2006 10:42 AM