Daikin EWAD300MBYNN [21/452] Esie 05 07 general outline

Daikin EWLD240MBYNN [21/452] Esie 05 07 general outline
ESIE 05-07 General Outline
Part 1 – System Outline 1–9
3
1
4
5
Notes 1. Nominal cooling capacity at Eurovent conditions: Evaporator 12°C/7°C; Condenser 30°C/35°C.
2. Heating capacity for conditions: Evaporator 12°C/7°C; Condenser 40°C/45°C.
3. Nominal cooling power input at Eurovent conditions: Evaporator 12°C/7°C; Condenser
30°C/35°C.
4. Heating power input for conditions: Evaporator 12°C/7°C; Condenser 40°C/45°C.
5. Min. required water volume for standard thermostat setting and at nominal conditions.
6. Piping connections are delivered with victaulic joint and counterpipe for welding.
7. Dimension values between brackets include installation space of delivered filter.
Oil charge volume
7.5 l 10 l
14 l
10 l
2 x 10 l
10 + 14 l 2x14 l
No. of circuits 1 2
Dimensions
(h x w (7) x d (7))
1018 x 2681
(3051) x
930 mm
1018 x 2681 (3254) x 930 mm
2000 x 2681 (3254) x 930 mm
Weight
Machine weight
1000 kg 1273 kg 1527 kg 1623 kg 2546 kg 2800 kg 3034 kg 3150 kg 3346 kg
Operation weight 1032 kg 1318 kg 1588 kg 1693 kg 2636 kg 2906 kg 3156 kg 3281 kg 3485 kg
Casing
Colour
Ivory white / Munsell code 5Y7.5/1 / ± RAL 7044
Material
Polyester coated galvanised steel plate
Sound power
level
91 dBA 95 dBA 96 dBA 98 dBA 99 dBA
Safety devices
Q Double PED approved high pressure switches
Q Low pressure protection
Q Pressure relief valve
Q Compressor motor thermal protector
Q Compressor motor overcurrent relay
Q Discharge temperature protector
Q Freeze up protection
Q Recycling and quard timer
Q Reverse phase protector/flow switch
Model
EWWD
120MBYNN
EWWD
180MBYNN
EWWD
240MBYNN
EWWD
280MBYNN
EWWD
360MBYNN
EWWD
440MBYNN
EWWD
500MBYNN
EWWD
520MBYNN
EWWD
540MBYNN
ESIE05-07.book Page 9 Wednesday, October 11, 2006 10:42 AM

Содержание