Daikin EWAD300MBYNN Сервис мануал онлайн [172/452] 402578

Daikin EWAP400MBYN Сервис мануал онлайн [172/452] 524348
Wiring Layout ESIE 05-07
1–160 Part 1 – System Outline
Power supply RS485 connection (Expansion board A11P) Analogue input
Analogue output
(Converted to digital outputs = DO)
Digital input
J1-G: 24Vac
J1-G0: Refer-
ence (GND)
J11-TX-
J11-TX+
J11-GND
Power supply:
J1-G: 24Vac
J1-G0: Reference (GND)
Digital output:
J4 (ID1-IDC1):
Flowswitch C2
Analogue input:
J9 (B1-GND): Capacity feedback of C1
J9 (B2-GND): Capacity feedback of C2
J2 (B1-VDC): High pressure C1
J2 (B2-VDC): Low pressure C1
J2 (B3-GND): Changeable AI1
J3 (B4-BC4): Evap Inlet water sensor
J3 (B5-BC5): Evap mixed outlet water t°
J6 (B6-GND): Cond Inletwater sensor
J6 (B7-VDC): High pressure C2
J6 (B8-VDC): Low pressure C2
J20 (B9-BC9): Evap Outlet water sensor C1
J20 (B10-BC10: Evap Outlet water sensor C2
J4 (VG0-Y1): loadup ctrl motor C1
J4 (VG0-Y2): loaddown ctrl motor C1
J4 (VG0-Y3): loadup ctrl motor C2
J4 (VG0-Y4): loaddown ctrl motor C2
J5 (ID1-IDC1): High pressure switch C1
J5 (ID2-IDC1): Reverse phase protector C1
J5 (ID3-IDC1): Overcurrent relay C1
J5 (ID4-IDC1): Discharge thermal prot C1
J5 (ID5-IDC1): Compr thermal prot C1
J5 (ID6-IDC1): Emergency stop
J5 (ID7-IDC1): Flowswitch
J5 (ID8-IDC1): Changeable DI 1
J7 (ID9-IDC9): Changeable DI 2
J7 (ID10-IDC9): Changeable DI 3
J7 (ID11-IDC9): Changeable DI 4
J7 (ID12-IDC9): High pressure switch C2
J8 (ID13-IDC13): Reverse phase protector C2
J8 (ID14-IDC13): Overcurrent relay C2
J19 (ID15-IDC15): Discharge thermal prot C2
J19 (ID16-IDC15): Compr thermal prot C2
Digital output Overview of changeable digital inputs DI 1-2-3-4 Overview of changeable digital outputs DO1-2 Overview of changeable analog input AI 1:
J12 (C1-NO1): Compr star C1
J12 (C1-NO2): Compr delta C1
J12 (C1-NO3): Compr on C1
J13 (C4-NO4): 12 C1
J13 (C4-NO5): --
J13 (C4-NO6): --
J14 (C7-NO7): Alarm
J15 (C8-NO8): Pump
J16 (C9-NO9): --
J16 (C9-NO10): --
J16 (C9-NO11): --
J17 (C12-NO12): Changeable DO 1
J18 (C13-NO13): Changeable DO 2
J21 (C14-NO14): Compr star C2
J21 (C15-NO15): Compr delta C2
J22 (C16-NO16): Compr on C2
J22 (C16-NO17): 12 C2
J22 (C16-NO18): --
J5 (ID8-IDC1):
J7 (ID9-IDC9):
J7 (ID10-IDC9):
J7 (ID11-IDC9):
Dual setpoint / Remote On -Off / enable / disable
capacity limitation 1-2-3-4
J17 (C12-NO12):
J18 (C13-NO13):
2nd evaporator pump / condenser pump / general oper-
ation / 100 capacity / reversing valve
J2 (B3-GND): Setp Signal 0-1V / 0-10V / 0-20mA /
4-20mA (only standalone unit or Slave1) / Evap. Outlet
water sensor DICN (only Master)

Содержание

Скачать