The Digital Controller For Large chillers ESIE 05-07
2–156 Part 2 – Functional Description
3
1
2
4
5
Screen 14 This screen shows the status of the changeable digital input and the digital outputs.
Screen 15 This screen shows the status of the In/Outputs of the EEV
Only if 1 or 2 electronic expansion valves are present on the unit.
Line n° Display Description Possible settings Possible status
1
CHANG.
INP/OUTPUTS
Screen title
2 DI4 XXXX:XXXX Changeable digital
input 4 + status of input
NONE
DUAL SETPOINT
REMOTE ON/OFF
REMOTE
COOL/HEAT
CAP. LIMIT 1
CAP. LIMIT 2
CAP. LIMIT 3
CAP. LIMIT 4
LOW NOISE
STATUS
HEAT REC:
SETP.1/SETP.2
ON/OFF
COOL/HEAT
NO LIM/LIMIT
NO LIM/LIMIT
NO LIM/LIMIT
NO LIM/LIMIT
N/Y
OPEN/CLOSED
NO REQ/REQ
3 DO1 XXXXXXX Changeable digital out-
put 1 + status of output
NONE(OPEN)
1(CLOSED)
2ND EVAP PUMP
CONDENSER
PUMP
100% CAPACITY
FREE COOLING
GEN.OPERATION
REV.VALVE(C/H)
EVAPHEATERT.:
HR COND PUMP:
O/C
(Open/Closed)
4 DO2 XXXXXXX Changeable digital out-
put 1 + status of output
Line n° Display Description Possible settings
1 EEV1 (2) IN/OUTPUTS Screen title
2 BATTERY: Status of the battery DISCONNECTED
HIGH INT.RES
NOT RECHARGE
DOWN
OK
3 VALVE POSITION The position of the elec-
tronic expansion valve
0 - 9999
ESIE05-07.book Page 156 Wednesday, October 11, 2006 10:42 AM