Daikin EWAH710TZ-XSB2 [22/102] Ewah tz ssb

Daikin EWAH580TZ-XSB2 [22/102] Ewah tz ssb
21/100
TECHNICAL SPECIFICATIONS
EWAH~TZ-SSB
MODEL
EWAH820TZ
SSB2
EWAH920TZ
SSB2
EWAH980TZ
SSB2
EWAHC10TZ
SSB2
COOLING PERFORMANCE
Capacity - Cooling
821
915
982
1,063
Capacity control - Type
Stepless
Stepless
Stepless
Stepless
Capacity control - Minimum capacity %
10
10
10
10
Unit power input - Cooling
280
321
341
378
EER
2.93
2.85
2.88
2.81
ESEER
4.85
4.83
4.81
4.99
IPLV
5.72
5.70
5.81
5.86
SEASONAL ENERGY EFFICIENCY ****
SEER (12/7°C)
5.248
5.278
5.206
5.13
η
s cool
(12/7°C) %
206.92
208.12
205.24
202.2
DIMENSIONS
Height
2540
2540
2540
2540
Width
2282
2282
2282
2282
Length
7787
8687
9587
9587
WEIGHT
Unit Weight
6942.8
7262.2
7553
7553
Operating Weight
7438.8
7758.2
8038
8006
WATER HEAT EXCHANGER
Type *
S&T
S&T
S&T
S&T
Water Volume
496
496
485
453
Water flow rate
39.2
43.7
47.0
50.8
Water pressure drop***
31.2
38.0
45.7
34.7
AIR HEAT EXCHANGER
Type *
MCH
MCH
MCH
MCH
FAN
Type *
DPT
DPT
DPT
DPT
Drive *
On/Off
On/Off
On/Off
On/Off
Diameter
800
800
800
800
Nominal air flow
69792
78516
87240
87240
Quantity
16
18
20
20
Speed
700
700
700
700
Motor input
13.8
15.6
17.3
17.3
COMPRESSOR
Oil charge
38.0
38.0
38.0
38.0
Quantity
2
2
2
2
SOUND LEVEL**
Sound Power - Cooling
105
106
107
108
Sound Pressure level@1m distance -
dB(A)
Cooling
84
85
85
86
REFRIGERANT CIRCUIT
Refrigerant type
R1234ze
R1234ze
R1234ze
R1234ze
Refrigerant charge
116.8
131.2
146
146
N. of circuits
2
2
2
2
PIPING CONNECTIONS
Evaporator water inlet/outlet
219.1
219.1
219.1
219.1
All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient
35.0°C, unit at full load operation; operating fluid: Water; fouling factor = 0.
(*)PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter - BRS:
Brushless
(**) Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1
for Eurovent certified units. The certification refers only to the overall sound power level, the sound pressure is calculated from the sound power level and
are for information only and not considered binding. The minimum capacity indicated is referred to unit operating at standard Eurovent conditions.
Dimensions and weights are for indication only and not considered binding. Before designing the installation, consult the official drawings available from
the factory at request. All the data are referred to standard unit without options. All data are subject to change without notice.
(***) The value refers to the pressure drops in the evaporator only.
(****) In accordance with standard EN14825:2013, comfort low temperature, average climate. SEER and ηs values applicable Ecodesign regulation: (EU)
No 2016/2281.