Daikin EWAH710TZ-XSB2 [61/102] Ewah tz xrb

Daikin EWAH710TZ-XSB2 [61/102] Ewah tz xrb
60/100
SOUND LEVELS
EWAH~TZ-XRB
Sound pressure level at 1 m from the unit (rif. 2 x 10-5 Pa)
Power db
(A)
MODEL
63 Hz
250 Hz
500 Hz
2000 Hz
4000 Hz
8000 Hz
db(A)
180
70.0
66.0
69.0
59.0
52.0
44.0
69
89
220
70.6
66.6
69.6
59.6
52.6
44.6
70
90
270
72.9
69.9
72.9
62.9
54.9
47.9
73
92
300
72.8
69.8
72.8
62.8
54.8
47.8
73
93
350
70.7
67.7
70.7
60.7
52.7
45.7
71
92
390
70.8
67.8
70.8
60.8
52.8
45.8
71
92
430
71.0
68.0
71.0
61.0
53.0
46.0
71
92
480
71.5
68.5
71.5
61.5
53.5
46.5
72
93
580
74.6
71.6
74.6
64.6
56.6
49.6
75
95
620
74.3
71.3
74.3
64.3
56.3
49.3
74
96
670
74.3
71.3
74.3
64.3
56.3
49.3
74
96
710
74.1
71.1
74.1
64.1
56.1
49.1
74
96
760
73.9
70.9
73.9
63.9
55.9
48.9
74
96
820
56.3
65.1
72.8
64.4
56.3
48.9
73
95
930
57.0
65.8
73.5
65.1
57.0
49.6
73
96
990
57.5
66.3
74.0
65.6
57.5
50.1
74
96
Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and
Eurovent 8/1 for Eurovent certified units. The certification refers only to the overall sound power level.
The sound data in the Octave band spectrum is for intended for reference only and not considering binding.
The sound pressure is calculated from the sound power level and are for information only and not considered binding.
The data are referred to the standard unit without options.

Содержание