D–EIMAC01502–18_02EN - 14/23
5.6 Sound protection
When sound levels require special control, great care must be exercised to isolate the unit from its base by appropriately
applying anti-vibration elements (supplied as an option). Flexible joints must be installed on the water connections, as well.
5.7 Water piping
Piping must be designed with the lowest number of elbows and the lowest number of vertical changes of direction. In this way, installation
costs are reduced considerably and system performance is improved.
The water system must have:
1. Anti-vibration mountings in order to reduce transmission of vibrations to the structures.
2. Isolating valves to isolate the unit from the water system during maintenance.
3. Flow switch, in order to protect the chiller must be protected against freezing by continuous monitoring of the water flow in the
evaporator. In most cases, on-site the flow switch is set to produce an alarm only when the water pump switches OFF and the water
flow fall to zero. it is recommended to adjust the flow switch in order to produce a “Water Loss Alarm” when the water flow reaches
50% of the nominal value, in this case the evaporator is protected against the freezing and the flow switch can detect the water filter
clogging.
4. Manual or automatic air venting device at the system’s highest point.; drain device at the system’s lowest point.
5. Neither the evaporator nor the heat recovery device must be positioned at the system’s highest point.
6. A suitable device that can maintain the water system under pressure (expansion tank, etc.).
7. Water temperature and pressure indicators to assist the operator during service and maintenance.
8. A filter or device that can remove particles from the fluid. The use of a filter extends the life of the evaporator and pump and helps to
keep the water system in a better condition. The water filter must be installed as close as possible to the chiller, as in Figs. 8
and 9. If the water filter is installed in another part of the water system, the Installer has to guarantee the cleaning of the water pipes
between the water filter and the evaporator.
Recommended maximum opening for strainer mesh is:
• 0,87 mm (DX S&T)
• 1,0 mm (BPHE)
• 1,2 mm (Flooded)
9. Evaporator has an electrical resistance with a thermostat that ensures protection against water freezing at ambient temperatures as
low as -16°C.
All the other water piping/devices outside the unit must therefore be protected against freezing.
10. The heat recovery device must be emptied of water during the winter season, unless an ethylene glycol mixture in appropriate
percentage is added to the water circuit.
11. If case of unit substitution, the entire water system must be emptied and cleaned before the new unit is installed. Regular tests and
proper chemical treatment of water are recommended before starting up the new unit.
Содержание
- Air cooled chiller with screw compressor 1
- Contents 2
- D eimac01502 18_02en 2 23 2
- List of figures 2
- Original instructions 2
- D eimac01502 18_02en 3 23 3
- D eimac01502 18_02en 4 23 4
- D eimac01304 17en 5 23 5
- Introduction 5
- D eimac01502 18_02en 6 23 6
- General information 6
- Operating limits 6
- Receiving the unit 6
- D eimac01502 18_02en 7 23 7
- D eimac01502 18_02en 8 23 8
- Mechanical installation 8
- D eimac01502 18_02en 9 23 9
- D eimac01502 18_02en 10 23 10
- D eimac01502 18_02en 11 23 11
- D eimac01502 18_02en 12 23 12
- D eimac01502 18_02en 13 23 13
- D eimac01502 18_02en 14 23 14
- Sound protection when sound levels require special control great care must be exercised to isolate the unit from its base by appropriately applying anti vibration elements supplied as an option flexible joints must be installed on the water connections as well 5 water piping 14
- The water system must have 14
- D eimac01502 18_02en 15 23 15
- D eimac01502 18_02en 16 23 16
- D eimac01502 18_02en 17 23 17
- Electrical installation 17
- Maintenance 17
- Operation 17
- D eimac01502 18_02en 18 23 18
- D eimac01502 18_02en 19 23 19
- D eimac01502 18_02en 20 23 20
- Periodic obligatory checks and starting up of appliances under pressure 20
- Service and limited warranty 20
- D eimac01502 18_02en 21 23 21
- Important information regarding the refrigerant used 21
- D eimac01502 18_02en 22 23 22
- Disposal 22
- D eimac01502 18_02en 23 23 23
- Daikin applied europe s p a 23
- Via piani di santa maria 72 00072 ariccia roma italia tel 39 06 93 73 11 fax 39 06 93 74 014 http www daikinapplied eu 23
Похожие устройства
- Daikin EWADH15T-XRC3 Инструкция по монтажу
- Daikin EWADC17T-XRC3 Инструкция по монтажу
- Daikin EWADC19T-XRC3 Инструкция по монтажу
- Daikin EWADH10T-XLC2 Инструкция по монтажу
- Daikin EWADH11T-XLC2 Инструкция по монтажу
- Daikin EWADH13T-XLC2 Инструкция по монтажу
- Daikin EWADH16T-XLC3 Инструкция по монтажу
- Daikin EWADH18T-XLC3 Инструкция по монтажу
- Daikin EWADC20T-XLC3 Инструкция по монтажу
- Daikin EWAD350T-XLC2 Инструкция по монтажу
- Daikin EWAD380T-XLC2 Инструкция по монтажу
- Daikin EWAD400T-XLC2 Инструкция по монтажу
- Daikin EWAD420T-XLC2 Инструкция по монтажу
- Daikin EWAD440T-XLC2 Инструкция по монтажу
- Daikin EWAD490T-XLC2 Инструкция по монтажу
- Daikin EWAD540T-XLC2 Инструкция по монтажу
- Daikin EWAD570T-XLC2 Инструкция по монтажу
- Daikin EWAD730T-XLC2 Инструкция по монтажу
- Daikin EWAD820T-XLC2 Инструкция по монтажу
- Daikin EWAD950T-XLC2 Инструкция по монтажу