Daikin EWADC13T-XRC2 [21/23] Important information regarding the refrigerant used

Daikin EWAD540T-XRC2 [21/23] Important information regarding the refrigerant used
DEIMAC0150218_02EN - 21/23
11 IMPORTANT INFORMATION REGARDING THE REFRIGERANT USED
This product contains fluorinated greenhouse gases. Do not vent gases into the atmosphere.
Refrigerant type: R134a
GWP(1) value: 1430
(1)GWP = global warming potential
The refrigerant quantity necessary is indicated on the unit name plate.
Periodical inspections for refrigerant leaks may be required depending on European or local legislation.
Please contact your local dealer for more information.
11.1 Factory and Field charged units instructions
The refrigerant system is charged with fluorinated greenhouse gases and the refrigerant charge is impressed on the plate,
shown below, which is applied inside the electrical panel.
Fill in with indelible ink the refrigerant charge label supplied with the product as following instructions:
- the refrigerant charge for each circuit (1; 2; 3) added during commissioning (on-site charging)
- the total refrigerant charge (1 + 2 + 3)
- calculate the greenhouse gas emission with the following formula:
-
𝐺𝑊𝑃 ∗ 𝑡𝑜𝑡𝑎𝑙 𝑐ℎ𝑎𝑟𝑔𝑒
[
𝑘𝑔
]
/1000
(use the GWP value mentioned on the greenhouse gases label. This GWP value is based on the 4th IPCC
Assessment Report.)
a Contains fluorinated greenhouse gases
b Circuit number
c Factory charge
d Field charge
e Refrigerant charge for each circuit (according to the number of circuits)
f Total refrigerant charge
g Total refrigerant charge (Factory + Field)
h Greenhouse gas emission of the total refrigerant charge expressed
as tonnes of CO2 equivalent
m Refrigerant type
n GWP = Global Warming Potential
p Unit serial number
In Europe, the emission of greenhouse gases of the total refrigerant charge in the system
(expressed in tonnes of equivalent CO
2
) is used to determine the frequency of maintenance
interventions. Follow the applicable legislation.