662 Installation of Outdoor Units
7.2 Wiring Connection Example for Whole System
1. Power supply
2. Main switch
3. Earth leakage circuit breaker
4. Fuse
5. Outdoor unit
6. COOL/HEAT selector
7. Remote controller
8. Indoor unit
Make sure the weak electric wiring (i.e. for the remote controller, between units, etc.) and the power wiring do not
pass near each other, keeping them at least 50 mm apart.
Proximity may cause electrical interference, malfunctions, and breakage.
Be sure to connect the power wiring to the power wiring terminal block and secure it as described in “7-5 Power
Wiring Connection Procedure”.
Transmission wiring should be secured as described in “7-4 Transmission Wiring Connection Procedure”.
Secure wiring with clamp such as insulation lock ties to avoid contact with piping.
Shape the wires to prevent the structure such as the EL. COMPO. BOX lid deforming. And close the cover firmly.
5HP type can not compose multi system.