INSTALLATION INSTRUCTIONS
The DHW and CH lters are housed in special extractable cartridges. The CH cartridge is located on the CH return line
(gure 16F) while the DHW cartridge is on the cold water input (gure 16E). To clean the lters, proceed as described below:
switch off the boiler;
shut the DHW inlet tap
drain the water in the CH circuit by opening tap A in gure 16.
remove the clip (1-E/F) from the lter as illustrated in the gure and take out the cartridge (2-E/F) containing the lter,
taking care not to apply excessive force;
to extract the heating lter cartridge, rst remove the 3-way valve motor (1-2G - gure 16);
eliminate any impurities and deposits from the lter;
reposition the lter in the cartridge and put it back into its housing, securing it with the clip.
to change the DHW NTC sensor, see gure 16D.
WARNING
when replacing and/or cleaning the O-rings on the hydraulic assembly, only use Molykote 111 as a lubricant, not oil or grease.
30. CLEANING THE FILTERS
The DHW circuit can be cleaned without removing the water-water heat exchanger if the assembly is tted with the special
tap (available on request) located on the DHW outlet. To clean, proceed as follows:
Close the DHW inlet tap;
Drain the DHW system by opening a hot water tap;
Close the DHW outlet tap;
Remove the clip 1E in gure 16;
Remove the lter (2E gure 16);
to change the DHW NTC sensor, see gure 16D.
If the special tap is not supplied, dismount the water-water heat exchanger, as described in the next section, and clean it
separately. Remove the scale from the seat and relative NTC sensor tted on the DHW circuit (gure 16D).
To clean the exchanger and/or DHW circuit, use Cillit FFW-AL or Benckiser HF-AL.
31. REMOVING SCALE FROM THE DHW CIRCUIT