Daikin CDXS25EAVMT [382/456] Malfunction of thermistor for outdoor air r1t

Daikin CDXS25EAVMT [382/456] Malfunction of thermistor for outdoor air r1t
Troubleshooting for Outdoor Unit SiEN18-622
370 Troubleshooting
7.9 Malfunction of Thermistor for Outdoor Air (R1T)
Remote Control
Display
H9
Applicable
Models
AII outdoor unit models
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by the outdoor air thermistor.
Malfunction
Decision
Conditions
When the outside air temperature thermistor has short circuit or open circuit.
Supposed
Causes
Defect of thermistor (R1T) for outdoor air
Defect of outdoor unit PCB (A1P)
Troubleshooting
Refer to “Thermistor Resistance / Temperature Characteristics” table on P407.
(V3070)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
NO
NO
YES
YES
Connector is
connected to X11A
ofoutdoor PC board
(A1P).
Connect the connector and turn
on again.
Replace the thermistor (R1T).
Replace outdoor unit PC board
(A1P).
Resistance
is normal when
measured after
disconnecting the
thermistor (R1T) from
the outdoor unit PC
board. (3.5kΩ
to 360kΩ)