Daikin CDXS25EAVMT [405/456] Troubleshooting

Daikin CDXS25EAVMT [405/456] Troubleshooting
SiEN18-622 Troubleshooting for Outdoor Unit
Troubleshooting 393
Troubleshooting
(V3187)
Caution
YES
YES
NO
YES
YES
NO
NO
YES
NO
NO
NO
NO
YES
NO
NO
YES
YES
YES
NO
YES
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Has the
indoor or
outdoor unit PC
board been replaced, or
has the indoor - outdoor
or outdoor - outdoor
unit transmission
wiring been
modified?
All
indoor unit remote
controls of the same
refrigerant system
display"U4."
Reset the power supply.
Outdoor
unit PC board
microcomputer monitor
(HAP) blinks.
Operation ready
lamp (H2P) is
blinking.
Lamp does
not go off for 12 minutes
or more.
Is
indoor - outdoor
and outdoor - outdoor
unit transmission
wiring normal?
Is indoor-
outdoor and outdoor
-outdoor unit transmission
wiring normal?
The
voltage between
terminals L1 and N of the
outdoor unit PC board
is 220~240 V.
The fuse on the
outdoor unit's PC board
isburnt.
The
secondary voltage of
the tran
sformer is
about 22~24 V.
Push and hold the RESET
button on the master outdoor
unit PC Board for 5 seconds.
* The unit will not operate for
up to 12 mintutes
Replace the indoor unit
PC board.
Fix the indoor/outdoor unit
transmission wiring.
Supply 220~240 V.
Replace the fuse.
Replace the transformer.
Replace outdoor unit PC
board (A1P).
Push and hold the RESET
button on the outdoor
unit
PC board for 5 seconds.
Fix the indoor/outdoor unit
transmission wiring.
Replace the outdoor unit
PC board (A1P).