Daikin CDXS25EAVMT [384/456] Malfunction of thermistor r3t r5t for suction pipe1 2

Daikin CDXS25EAVMT [384/456] Malfunction of thermistor r3t r5t for suction pipe1 2
Troubleshooting for Outdoor Unit SiEN18-622
372 Troubleshooting
7.11 Malfunction of Thermistor (R3T, R5T) for Suction
Pipe1, 2
Remote Control
Display
J5
Applicable
Models
AII outdoor unit models
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by the thermistor for suction pipe 1, 2.
Malfunction
Decision
Conditions
When a short circuit or an open circuit in the thermistor for suction pipe 1, 2 are detected.
Supposed
Causes
Defect of thermistor (R3T, R5T) for outdoor unit suction pipe
Defect of outdoor unit PCB (A1P)
Troubleshooting
Refer to thermistor resistance / temperature characteristics table on P407.
(V3073)
Caution
NO
NO
YES
YES
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Connect the thermistor and
turn on again.
Replace the thermistor
(R3T, R5T).
Replace outdoor unit PC board
(A1P).
Connector
of the thermistor for
suction pipe1, 2 is
connected to outdoor
unit PC board
(A1P).
Resistance is
normal when
measured after
disconnecting the thermistor
(R3T, R5T) from
the outdoor unit PC
board. (3.5kΩ~
360KΩ)