Troubleshooting Si04-703A
98 Service Diagnosis
Troubleshooting
Check No.01
Refer to P.130
Turn off power supply and
disconnect fan motor
connector, then turn
power ON.
Turn off power supply and
disconnect fan motor
connector, then turn
power ON again.
Check No.01
Check output of fan
motor connector
Check No.01
Check output of fan
motor connector
Check No.01
Check output of fan
motor connector
Check No.01
Check output of fan
motor connector
(R7133)
YES
YES
NO
YES
YES
NO
YES
NO
NO
YES
NO
YES
NO
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Replace fan motor.
Replace indoor unit
PCB.
Replace indoor unit
PCB.
Note : Motor may
break when
the motor
connector is
disconnected
while
remaining
power supply
.
Replace fan motor.
Replace indoor unit
PCB.
Replace indoor unit
PCB.
Replace fan motor.
Replace
fan motor
and indoor PCB.
Does fan rotate
smoothly?
Does it rotate?
Is rotation
number command
pulse generated?
Is motor
power voltage DC
200V generated?
Is motor
control power
voltage DC 15V
generated?
Is
rotation
number command
voltage DC 1~6V
generated?
Is rotation
number command
pulse generated?
Turn off power supply
and rotate fan by hand.
Turn power ON and
operate fan.
Stop fan motor.