Si04-703A Troubleshooting
Service Diagnosis 101
Troubleshooting
Check No.10
Refer to P.135
Check the voltage of the indoor
unit-outdoor unit connection wires
between No. 1 and No. 3, and
between No 2 and No. 3.
Check No.10
Check power supply waveform.
YES
YES
Replace indoor unit control
PCB .
Locate the cause of the
disturbance of the power supply
waveform, and correct it.
NO
(R8360)
NO
YES
YES
NO
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
YES
NO
Correct the indoor unit-outdoor
unit connection wires.
Diagnose the outdoor unit.
Replace the connection wires
between the indoor and
outdoor units.
Replace fan motor and outdoor
unit PCB .
Does fan rotate
smoothly?
Is LED A flashing?
Is the voltage 0 V?
Is there any disturbance?
Is there any wiring error?
Check the indoor unit-outdoor unit
connection wires.
Check the outdoor unit's LED A.
Rotate fan by hand.