3.2.4 <KDDJ55X160> Fresh Air Intake Kit
The fresh air is taken into the unit by the indoor unit fan or duct fan, which is field supplied. The location of fresh air intake port will be
changeable by installing the duct fan.
KDDJ55X160
Contents
Necessary tools
2. When installing this kit
,
duct
(
Nominal dia. : φ75
)
is required on site.
Remarks :
Prior to installation
,
make sure you have the complete kit of parts.
Shape
1. This kit can be installed to the Ceiling mounted cassette type
(
Multi-flow
)
.
Philips head screw driver
,
nipper
,
cutter etc.
Name
Q'ty
Installation procedures of Duct flange
The method of installation varies with indoor unit type.
The unit type can be distinguished by the position of knockout hole.
1. Cut off the knockout hole on the side plate.
(
Fig. 1
)
1
Duct Flange
1 piece 4 pieces
2
M4×12
Screws
3
Insulation for Duct Flange
1 piece
Knockout hole
4
Insulation for Opening of
Cut off only side plate.
There is no inner insulation.
1 piece
Unit
Cut it off
Side plate
with nipper.
Slit
Side plate
Ref. pipe
5
Installation Manual
1 piece
Drain pipe
Fig.1