FUNCTIONAL SPECIFICATIONS
INTRODUCTION
When the AirzoneBACnet Interface is used in a BACnet/IP network, it operates as a BACnet interpreter using the services defined
by the BACnet to return the status of the Airzone system. It also sends configuration commands to them, in response to requests
from a BACnet building management system (BMS) (i.e., BACnet client) which support the BACnet (ISO16484-5,
ANSI/ASHRAE135) protocol.
The Airzone BACnet Interface is a plug and play device, which, when connected to the Main Control Board and to a BACnet
network, it configures itself and configures the main board to work with the BACnet network.
When the Airzone BACnet Interface is connected to the Main Control Board, a new item appears in the user menu. From the
main screen, press the icon , select the Information parameter and press the Webserver menu.
AVAILABLE SERVICES
- Read Property.
- Multiple Read Property.
- Write Property.
- Multiple Write Property.
- COV (Change of Value).
- Dynamic Device Binding (who-is, i-am, who-has, i-have).
- DCC (Device Communication Control).
- UTC Time synchronization.
Note: The values of the parameters are updated every second.
Содержание
- Installation s manual 1
- Table of contents 2
- Outline and features 3
- Overview 3
- System outline 3
- 20 to 70 c 4
- Ethernet 4
- I máx 200 ma 4
- Non condensing 4
- Specifications and device elements 4
- Standard t568b 4
- To 50 c 4
- Utp cat 6 4
- V máx 4
- X40x39 mm 4
- Available services 5
- Functional specifications 5
- Introduction 5
- Bacnet interface configuration 6
- Installation and configuration 6
- Installation on the control board 6
- Status menu 6
- Device id 7
- Settings menu 7
- Objects 8
- Objects list 8
- Supported object type 8
- Flexa 3 innobus pro6 easyzone systems 9
- Acuazone innobus pro32 systems 11
- Air radiant demand 19
- Common to all objects 19
- Detailed description of the objects 19
- Z alarm input 19
- Z humidity 19
- Z on off 19
- Z radiant stage 19
- Z room temperature 19
- Z fancoil speed 20
- Z operation mode 20
- Z set point 20
- The airzone bacnet interface cannot be connected i 21
- The airzone bacnet interface cannot be connected ii 21
- The airzone system does not detect the airzone bacnet interface 21
- Troubleshooting 21
- How to set the pc s ip address 22
Похожие устройства
- Daikin AZER6DAISL01S2 Инструкция по эксплуатации
- Daikin EHBH04CB3VU Руководство по эксплуатации
- Daikin EHBH04CB3VU Руководство по применению для пользователя
- Daikin EHBH04CB3VU Приложение к руководству для дополнительного оборудования
- Daikin EHBH04CB3VU Инструкция по монтажу
- Daikin EHBH04CB3VU Инструкция по эксплуатации
- Daikin EHBH04CBV Руководство по эксплуатации
- Daikin EHBH04CBV Руководство по применению для пользователя
- Daikin EHBH04CBV Приложение к руководству для дополнительного оборудования
- Daikin EHBH04CBV Инструкция по монтажу
- Daikin EHBH04CBV Инструкция по эксплуатации
- Daikin EHBH08CBV Руководство по эксплуатации
- Daikin EHBH08CBV Руководство по применению для пользователя
- Daikin EHBH08CBV Инструкция по монтажу
- Daikin EHBH08CBV Приложение к руководству для дополнительного оборудования
- Daikin EHBH08CBV Инструкция по эксплуатации
- Tecnoclima MB 60 Инструкция по эксплуатации
- Tecnoclima MB 60 Сертификат
- Tecnoclima MB 60 Каталог
- Tecnoclima MB 85 Инструкция по эксплуатации