5 Commissioning
Installation manual
13
RZAG71~140L7V1B
Split system air conditioners
4P418662-1 – 2016.02
The following field wiring has been carried out according
to this document and the applicable legislation:
▪ Between the local supply panel and the outdoor unit
▪ Between the outdoor unit and the indoor unit
There are NO missing phases or reversed phases.
The system is properly earthed and the earth terminals
are tightened.
The fuses or locally installed protection devices are
installed according to this document, and have not been
bypassed.
The power supply voltage matches the voltage on the
identification label of the unit.
There are NO loose connections or damaged electrical
components in the switchbox.
The insulation resistance of the compressor is OK.
There are NO damaged components or squeezed
pipes on the inside of the indoor and outdoor units.
There are NO refrigerant leaks.
The correct pipe size is installed and the pipes are
properly insulated.
The stop valves (gas and liquid) on the outdoor unit are
fully open.
5.2 To perform a test run
This task is only applicable when using the BRC1E52 or BRC1E53
user interface. When using any other user interface, see the
installation manual or service manual of the user interface.
NOTICE
Do not interrupt the test run.
INFORMATION
Backlight. To perform an ON/OFF action on the user
interface, the backlight does not need to be lit. For any
other action, it needs to be lit first. The backlight is lit for
±30seconds when you press a button.
1 Perform introductory steps.
# Action
1 Open the liquid stop valve (A) and gas stop valve (B)
by removing the stem cap and turning
counterclockwise with a hex wrench until it stops.
A B
2 Close the service cover to prevent electric shocks.
3 Turn ON power for at least 6hours before starting
operation to protect the compressor.
4 On the user interface, set the unit to cooling operation
mode.
2 Start the test run
# Action Result
1 Go to the home menu.
Cool
Set to
28°C
2 Press at least 4seconds. The Service Settings menu
is displayed.
3 Select Test Operation.
Return Setting
Service Settings 1/3
Test Operation
Maintenance Contact
Field Settings
Demand
Min Setpoints Differential
Group Address
4 Press. Test Operation is
displayed on the home
menu.
Cool
Return Setting
Test Operation
5 Press within 10seconds. Test run starts.
3 Check operation for 3minutes.
4 Check operation of the airflow direction.
# Action Result
1 Press.
Return Setting
Return Setting
Air Volume/direction
Air Volume Direction
Position 0
Low
2 Select Position 0.
Return Setting
Return Setting
Air Volume/direction
Air Volume Direction
Low
Position 0
3 Change the position. If the airflow flap of the
indoor unit moves,
operation is OK.
If not, operation is not OK.
4 Press.
The home menu is
displayed.
5 Stop the test run.
# Action Result
1 Press at least 4seconds.
The Service Settings menu
is displayed.
2 Select Test Operation.
Return Setting
Service Settings 1/3
Test Operation
Maintenance Contact
Field Settings
Demand
Min Setpoints Differential
Group Address
Содержание
- Installation manual 1
- Split system air conditioners 1
- Installation manual 2
- 551 emc 3
- Aib vinçotte nb0026 3
- Daikin europe n v 3
- Daikin tcf 33 04 2016 3
- Daikin tcfp 01 3
- Dekra nb0344 3
- Electromagnetic compatibility 2014 30 eu 3
- En60335 2 40 3
- Low voltage 2014 35 eu 3
- Machinery 2006 42 ec 3
- P329110 6g 3
- Pressure equipment 2014 68 eu 19 07 2016 3
- Pressure equipment 97 23 ec 18 07 2016 3
- Rzag71l7v1b rzag100l7v1b rzag125l7v1b rzag140l7v1b 3
- Aib vinçotte international n v diamant building a reyerslaan 80 b 1030 brussels belgium 4
- P329110 6g 4
- Shigeki morita director ostend 1st of april 2016 4
- About the box 5
- About the box 5 5
- About the documentation 5
- About the documentation 5 5
- About this document 5
- Commissioning 12 5
- Installation 6 5
- Installation site requirements of the outdoor unit 5
- Outdoor unit 5
- Preparation 5
- Preparation 5 5
- Preparing installation site 5
- Table of contents 5
- Technical data 14 5
- To remove the accessories from the outdoor unit 5
- About the minimum floor area 6
- Installation 6
- Mounting the outdoor unit 6
- To determine the minimum floor area 6
- To install the outdoor unit 6
- To provide drainage 6
- To provide the installation structure 6
- B a 4 ø6 mm 7
- Connecting the refrigerant piping 7
- Installation 7
- To connect the refrigerant piping to the outdoor unit 7
- To prevent the outdoor unit from falling over 7
- Ø6 mm 7
- Checking refrigerant piping setup 8
- Checking the refrigerant piping 8
- Installation 8
- To check for leaks 8
- To determine if oil traps are required 8
- About charging refrigerant 9
- Charging refrigerant 9
- Installation 9
- To perform vacuum drying 9
- About the refrigerant 10
- Charging refrigerant setup 10
- Installation 10
- To charge refrigerant 10
- To determine the additional refrigerant amount 10
- To determine the complete recharge amount 10
- About electrical compliance 11
- Connecting the electrical wiring 11
- Guidelines when connecting the electrical wiring 11
- Installation 11
- Specifications of standard wiring components 11
- To connect the electrical wiring on the outdoor unit 11
- To fix the fluorinated greenhouse gases label 11
- A b c d e 12
- Checklist before commissioning 12
- Commissioning 12
- Finishing the outdoor unit installation 12
- To check the insulation resistance of the compressor 12
- To finish the outdoor unit installation 12
- Commissioning 13
- To perform a test run 13
- Error codes when performing a test run 14
- Service space outdoor unit 14
- Technical data 14
- Piping diagram outdoor unit 15
- Technical data 15
- Wiring diagram outdoor unit 15
- Technical data 16
- Ceiling mounted 19
- Ceiling mounted uni 19
- Floor standing 19
- Floor standing uni 19
- Wall mounted 19
- Wall mounted uni 19
- Copyright 2016 daikin 20
- P418662 1 20
Похожие устройства
- Daikin RZAG71L7V1B Руководство по применению для установщика
- Daikin RZAG71L7V1B Общие правила техники безопасности
- Alpine X903D-ID Инструкция по эксплуатации
- Alpine X903D-S906 Руководство пользователя
- Alpine X903D-S906 Инструкция по эксплуатации
- Daikin RZAG125L7V1B Инструкция по монтажу
- Daikin RZAG125L7V1B Общие правила техники безопасности
- Daikin RZAG125L7V1B Руководство по применению для установщика
- Daikin RZAG100L7V1B Инструкция по монтажу
- Daikin RZAG100L7V1B Общие правила техники безопасности
- Daikin RZAG100L7V1B Руководство по применению для установщика
- Alpine X903D-V447 Руководство пользователя
- Alpine X903D-V447 Инструкция по эксплуатации
- Daikin RZAG140L7V1B Инструкция по монтажу
- Daikin RZAG140L7V1B Общие правила техники безопасности
- Daikin RZAG140L7V1B Руководство по применению для установщика
- Alpine INE-F904D Руководство пользователя
- Alpine INE-F904D Инструкция по эксплуатации
- Alpine X903D-F Инструкция по эксплуатации
- Alpine X903D-F Руководство пользователя